3S-Smart Software Solutions has an update to improper access control and relative path traversal vulnerabilities in its CoDeSys first published in January, 2013, according to a report with CISA.

Successful exploitation of these remotely exploitable vulnerabilities could allow an attacker with low skill levels to gain unauthorized access and obtain administrative privileges. In addition, public exploits are available. Researcher Reid Wightman, who discovered the vulnerabilities, validated the patch issued by 3S mitigates theses vulnerabilities.

The following 3S CoDeSys Runtime versions suffer from the issues:

  • CODESYS Control Runtime embedded: Versions prior to 2.3.2.8
  • CODESYS Control Runtime full: Versions prior to 2.4.7.40
  • CODESYS Control RTE: Versions prior to 2.3.7.17

The CoDeSys Runtime Toolkit is used in several vendor’s products worldwide.

Schneider Bold

In one vulnerability, the CoDeSys Runtime Toolkit does not require users to authenticate when connecting to the device. An attacker could obtain administrative privileges on the device by default. This could allow the attacker to compromise the availability, integrity, and confidentiality of the device.

CVE-2012-6068 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 9.8.

In addition, the CoDeSys Runtime Toolkit’s file transfer functionality does not perform input validation, which allows an attacker to access files and directories outside the intended scope. This may allow an attacker to upload and download any file on the device. This could allow the attacker to affect the availability, integrity, and confidentiality of the device.

CVE-2012-6069 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 10.0.

The product sees use in the critical manufacturing, commercial facilities, energy, and transportation systems sectors. It also sees action on a global basis.

Germany-based 3S recommends upgrading to the latest CoDeSys version, which is Version 3. Click here to download the latest version.

In addition, 3S released a patch which implements a password for authentication to the device.
Click here to download the patch from the CoDeSys Download Center. 3S also recommends the usage of standard security methods like firewalls or virtual private network (VPN) access to prevent unauthorized access to the controller.

CoDeSys Version 3.X is not affected by these vulnerabilities.