Critical infrastructure owners, operators, and integrators should remove publicly exposed PLCs and other operational technology (OT) from the Internet as soon as possible, CISA said.
Threat actors targeting exposed PLCs modified passwords to lock out operators and disconnected the PLCs by changing their IP addresses. This activity has resulted in boil water notices and sustained manual operations.
These threat actors are targeting water entities of all sizes.
Earlier this week, an attack briefly shut down a water plant in Braham, MN, Monday morning, city officials said. Three other communities reported attempted attacks on Monday: Maple Plain, Plymouth and South St. Paul. However, the state is saying 30 communities were a part of the attack.
Cellular Modens Targeted
Even water organizations with mature cybersecurity processes should validate their external connections, as this targeting activity includes cellular modems installed by operators, vendors, or system integrators that may not be documented or included in routine attack surface scans.
OT assets exposed to the Internet have an increased risk of defacement, configuration changes, operational disruptions, and, in severe cases, physical damage.
CISA recommends organizations implement the following mitigations:
- Disconnect the PLC from the Internet. Remote access for operational purposes should go through a VPN or gateway device, not directly to the PLC.
- Enable password protection and change default passwords.
- Allowlist IPs to only allow remote access from known engineering laptops or other critical OT assets.
After disconnecting PLCs from the internet, operators should ensure they have a known clean backup of the PLC image in case they end up locked out by a modified password.
Owners, operators, and integrators of Rockwell Automation MicroLogix 1400 PLCs should see Rockwell Automation’s notice, entitled, “Restoring Access to a MicroLogix 1400 Controller When the Password Is Unknown” for guidance addressing this activity.
To securely enable remote access to your OT systems, CISA recommends system owners, operators, and integrators see the following resources for guidance:
- CISA: Primary Mitigations to Reduce Cyber Threats to Operational TechnologyÂ
- United Kingdom’s National Cyber Security Center: Secure Connectivity Principles for Operational TechnologyÂ
For additional support, contact the Environmental Protection Agency’s Cybersecurity Technical Assistance Program for the Water Sector.