OSHA investigators found the 33-year-old employee of Wellborn Cabinet Inc. came into contact with a 277-volt circuit while replacing a light fixture in a paint booth on March 16.
Founded in 1961, Ashland-based Wellborn Cabinet is a family-owned business that manufactures kitchen and bath cabinets, and employs 1,200 workers.
OSHA cited Wellborn Cabinet with eight serious violations for not verifying that circuit elements and equipment parts were de-energized before allowing an employee to install light fixtures, and for failing to use energy isolating devices for hazardous energy.
“A worker’s family, friends and co-workers now grieve a terrible loss which might have been prevented had Wellborn Cabinet followed federal safety requirements,” said OSHA Area Director Ramona Morris in Birmingham. “Every worker has a right to a safe and healthful workplace and every employer is legally responsible for providing one. We encourage employers to contact us with questions about keeping their employees safe.”
In 2020, 126 workers lost their lives from exposure to electricity on the job, the Bureau of Labor Statistics reports.


Working on 277-volt lighting fixtures live is not uncommon albeit not safe.
Many 100W fixtures can be put on a 20A 277VAC branch circuit. When one needs to be worked on, shutting that circuit deenergizes up to 43 other fixtures. There’s a lot of pressure to work on them live to avoid shutting all the lights off in a production area.
Based on (277V X 16A) / 100VA = 44.32 or 44 total fixtures with a full ampacity rating of 0.8 X 20, or 16A.
The NEC doesn’t require individual energy isolation devices for all electrical equipment, but OSHA implies that they are needed by the requirements. This is a really on-going problem and needs to be addressed somehow. This applies to motors as well as other primary movers, using electrical energy.
The NEC did adopt a similar requirement for HVAC compressor units so that they can be deenergized by a maintenance mechanic by a local lockable isolation device.
I believe the US DOL should get on code panels and advocate for such devices rather than issue fines after the body cools to room temperature.