By Gregory Hale
Winds farms were not the only utility attacked this past December as a steam turbine and the process-water treatment system at a Polish combined heat and power (CHP) plant ended up shut down by attackers that gained entry via a private cellular network.

That attack came on the heels of the December Polish wind farm and large CHP plant hack, which destroyed equipment. A small CHP plant also fell victim to an attack and CERT Polska just released that information. The information on the attack became public during DEF CON in Las Vegas last week as Marcin Dudek, head of CERT Polska, presented details on the incident.

The plant in Poland supplies heat to 50,000 residents. The plant’s steam turbine and a water treatment system used to produce process water ended up shut down, interrupting the cogeneration process, in which electricity and heat generate simultaneously. Thanks to the prompt response of the CHP plant’s operators, the December 29 incident resulted only in a short-term outage and did not disrupt heat supplies to consumers.

CERT Polska disclosed the December 2025 incident on August 8 after an investigation lasting more than three months. Poland’s prime minister had said in January two CHP plants were hit. The small plant was the second.

Schneider Bold

“This was a first cyberattack against Poland’s energy sector in which the objective was purely destructive,” CERT Polska said in a report. “It also proved to be considerably more complex than initially believed, involving an additional event that had not previously been disclosed publicly and that likewise took place in December 2025.”

That event was the attack on the smaller CHP plant.

Free Communication

At the plant, there was a dedicated cellular data network managed by the distribution system operator (DSO). A configuration that allowed arbitrary devices on an access point name (APN) to communicate with one another let the attacker pivot from a compromised wind-farm network to a controller at the CHP plant.

The wind farm and the plant are separate facilities, and neither of them runs the network that linked them.

The report does not establish a software or hardware vulnerability as the cause of the intrusion, and investigators could not determine whether an issue in the Teltonika router ended up exploited.

Attack path

Attack path from the wind farm to the combined heat and power Plant.
Source: CERT Polska

However, based on further detailed analysis of the collected logs, investigators were able to identify the device from which the attacker had conducted their activities: A WAGO PFC200 PLC equipped with an integrated cellular modem, according to the report. As it turned out, the device suffered damage, and investigators could not recover data from it.

Investigators were able to obtain information indicating the device ended up used to communicate with the systems of the DSO. It had a SIM card operating within a dedicated private data transmission network (private APN) managed by the DSO.

“This discovery led to a painstaking analysis that ultimately allowed us to reconstruct the attack sequence,” investigators said in the report.

The WAGO controller reachable through the APN still had default admin credentials, while the private APN allowed client-to-client traffic. CERT said it found Polish organizations running private APNs commonly let any device on the network reach any other, according to the report.

Starts at Wind Farm

The attack path began at a wind farm, where a FortiGate device served as firewall and VPN concentrator. Its VPN ended up exposed to the Internet and allowed accounts without multi-factor authentication. The attacker had administrative privileges on the device and likely used them to obtain VPN credentials that could reach all network segments, according to the report.

The distribution operator required communications to the substation’s remote terminal unit to run over the serial DNP3.0 protocol. But no requirements ended up defined regarding the handling of the cellular router’s administrative interface. As a result, the router ended up configured with two physical interfaces: A serial link connected to the RTU and a second interface, Ethernet, connected to a VLAN managed by the central firewall compromised by the attacker.

The wind farm met the DNP3.0 requirement and still supplied the route in. That requirement governed how data travelled, not how the device carrying it ended up administered.

The router was a Teltonika RUTX50 whose default password had been changed during deployment. Investigators recovered repeated successful SSH logins but could not establish how the attacker obtained that password.

Mobile-operator logs led CERT to assess the attacker most likely used SSH tunneling through the router to reach the private APN.

Starting December 18, the attacker scanned the APN and found a WAGO PFC200 controller exposing its web administration interface with default admin credentials. Subsequent SSH activity found the service ended up enabled through that interface. CERT timestamp correlation assessed the attacker most likely tunneled through the WAGO into the plant’s OT network.

Wago controller

The WAGO PFC200 controller pictured after the attack.
Source: CERT Polska

On December 25, the attacker successfully connected to three Siemens PLCs over the S7 protocol, according to the report.

Attack Starts

On December 29, the attack inside the CHP network ran from 5:30 a.m. until 10:10 a.m., with plant recovery beginning at 7:30 a.m. That means when the recovery was going on, the attackers were still in the network for just over two and a half hours.

According to statements provided by CHP plant personnel, the Siemens PLCs ended up switched to STOP mode and protected with a password that prevented changes to their operating state and modification of the control logic. As a result, the steam turbine and the water treatment system used to produce process water shut down, leading to an interruption of the cogeneration process.

As part of the recovery efforts, the operators restored the affected devices to their factory settings and reloaded the available backups of the controllers’ logic. This approach helped reduce the duration of the outage but also resulted in the deletion of logs stored on the controllers.

Seven Moxa serial device servers and three switches also ended up factory-reset, given changed passwords and assigned unreachable IP addresses such as 127.0.0.1, according to the report. CERT said with a high degree of confidence the timing indicates attackers automated those actions.

During the attack, connections to the web administration interfaces of two ABB ACS series variable frequency drives also ended up observed. It was not possible to determine what actions, if any, the attacker performed on these devices, according to the report.

Other Attack Attempts

Network traffic logs also revealed unsuccessful attempts to connect to Schneider Electric ATV6xx variable frequency drives. The failure was most likely the result of incomplete reconnaissance, as the attacker attempted to connect to port 80/TCP while the devices’ web administration interfaces were listening on a different port, the report said.

The WAGO controller’s partition table ended up corrupted, leaving it unable to boot and yielding no useful logs. The Teltonika RUTX50 cellular router used to establish SSH tunnels ended up restored to its factory settings 30 minutes after the last observed activity in the CHP plant network. The attacker then changed the administrator password and set the device’s IP address to an unreachable value, 127.0.0.1, likely to impede its reconfiguration. The attacker also then factory-reset the FortiGate, causing its logs to be lost.

CERT said RutOS versions earlier than 7.07 retained their event database after a factory reset, which is why the SSH login records survived.

The attacker’s activity within the CHP plant network lasted for nearly five hours and concluded with access to the SCADA system’s web administration interface, most likely to assess the impact of the actions carried out.

Initially, the plant did not initially read this as an attack. Maintenance was underway, so the operator logged the interruption as probable contractor error and reported it for information only. CERT opened an incident because it already knew of similar events.

Recommendations

CERT Polska recommends entities using solutions based on private APNs should:

  • Conduct an audit of their private APN configuration. In particular, enabling client isolation between end devices connected to the APN.
  • Treat the private APN as an untrusted network in relation to the OT environment. On the OT side, connectivity to the private APN should be subject to network segmentation and traffic controls at least equivalent to those applied to corporate WAN connections.
  • Strictly limit communications between the OT network and the device acting as the gateway to the private APN. Only connections required to support defined business and technical functions should end up permitted, using allowlist-based rules.
  • Monitor traffic between the OT network and the private APN, with particular attention paid to deviations from the defined communication profile expected for the connection.
  • Implement centralized logging and monitoring of events generated by devices serving as gateways to the private APN, where such functionality has support.
  • Minimize the number of open ports accessible via interfaces reachable from the private APN. In particular, administrative services such as web management interfaces, SSH, or Telnet should not suffer from exposure.
  • Change default credentials for all services available on devices connected to the private APN, especially administrative services.
  • Include private APNs and the devices providing access to them within the scope of penetration tests, red team exercises, and security architecture reviews.