During an offshore regulatory inspection of a coiled tubing unit (CTU) layout and rig up, inspectors discovered a concerning issue with the rental generator/light plant powering the CTU, said officials at the Bureau of Safety and Environmental Enforcement (BSEE).

Specifically, investigators found evidence of tampering with the emergency shutdown (ESD) and spark arrestor system. The ESD ended up bypassed by removing the air intake hose, which had become clogged with black soot, causing it to collapse and leading to issues such as sputtering, smoking, and eventually engine failure.

The air intake hose was never re-installed, resulting in the continued bypass of the ESD. In addition, the inside of the generator/light plant had a coat of black soot due to a damaged muffler.

In response to these findings, the inspection team requested the operator (personnel on duty) test the ESD to confirm its functionality. The test revealed the ESD failed to properly shut down the power-generating unit, as designed.

Schneider Bold

It is crucial to note ESD systems are there to prevent unsafe operations by automatically shutting down equipment and offshore facility systems in the event of unsafe conditions. In this case, the ESD for the rental generator/ light should shut down the generator/light plant itself and the CTU.

The ESD system bypass placed personnel at additional risk for various hazards, including fire, explosion, inhalation, rotating equipment, moving equipment, pinch points, unexpected pressure releases, and dropped objects.

Immediate corrective actions should occur to rectify these safety concerns and ensure the proper functioning of the ESD system to mitigate risks effectively.

In addition, BSEE recommends operators and their contractors, where appropriate, consider doing the following:

Ensuring reviewed and approved Management of Change or Lock Out Tag Out procedures are in place, offering protection for the system or piece of equipment if the ESD must go in bypass for maintenance, testing, or troubleshooting purposes.

  • Examining rental equipment arriving onsite for obvious signs of damage, lack of maintenance, improper operation, over-heating, or over-pressure. Stopping the job until all such issues end up resolved, equipment has been successfully function tested, and is fully functional for operations.
  • Reviewing preventative maintenance records and ensuring adequate inspection and functional performance of rental equipment before use.
  • Providing instructions, training, competency assessment, and proper supervision to operators and maintenance personnel.

A rental generator/light plant on the left, of the right ESD for rental generator/light plant found in bypass.Source: BSEE

  • Ensuring compliance with 30 CFR 250.867 (a), (c), and (d) (Temporary quarters and temporary equipment) and 250.842(a)(2) and (3) (Approval of safety systems design and installation features).
  • Inspecting generators and critical equipment in accordance with BSEE regulations, ensuring all meet the minimum safety requirements and the recommendations provided by manufacturers. There should be documentation to maintain a clear record of equipment integrity and performance. Each inspection and test should verify:
    1. Inspections Were Performed at Appropriate Intervals: Inspecting generators and critical equipment at intervals specified by BSEE regulations and manufacturer guidelines to guarantee compliance and optimal functionality.
    2. Proper Documentation is Provided: Maintaining comprehensive records of each inspection and test, including:
    — Date of Inspection and Test: Clearly note the date when the inspection and testing occurred.
    — Equipment Identifier: Include the serial number or any unique identifier associated with the specific equipment that underwent inspection or testing.
    — Description: Provide a detailed description of the inspection or test procedures conducted to ensure clarity and accountability.
    — Inspection Results: Document the outcomes and findings of the inspection or test, including any issues, concerns, or areas that require corrective action.
  • Reviewing Safety Alert 432 BSEE Identifies Maintenance and Certification Issues of Rental Generators.