General Electric has a firmware upgrade available to handle cross-site scripting vulnerabilities in its Reason S20 Ethernet Switch, according to a report with CISA.
Successful exploitation of these remotely exploitable vulnerabilities, discovered by IOActive, could allow unauthorized accounts manipulation and allow for remote code execution.
The following versions of Reason S20 managed Ethernet switches suffer from the issues:
- S2020, All firmware versions prior to 07A06
- S2024, All firmware versions prior to 07A06
In one issue, the affected product is vulnerable to cross-site scripting (XSS), which may allow an attacker to trick application users into performing critical application actions that include, but are not limited to, adding and updating accounts.
CVE-2020-16242 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 6.1.
In addition, the affected product has a XSS vulnerability, which may allow attackers to trick users into following a link or navigating to a page that posts a malicious JavaScript statement to the vulnerable site, causing the malicious JavaScript to be rendered by the site and executed by the victim client.
CVE-2020-16246 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 6.1.
The product sees use mainly in the energy sector and it sees action on a global basis.
No known public exploits specifically target these vulnerabilities. However, an attacker with low skill level could leverage the vulnerabilities.
GE recommends S20 users upgrade to firmware Version 07A06 or higher to fix this vulnerability. Instructions on how to upgrade the firmware and verify its installation are available in the product user’s manual. Upgrading can be done by downloading the upgrade file directly from the GE website.