Successful exploitation of these vulnerabilities, discovered by Ritesh Kumar Kalle, Subhojeet Mukherjee, Hishamudeen of the Cybersecurity Research group, Hitachi India R&D Center, could result in impact on confidentiality, integrity and availability of the product.
The Hitachi Energy CoreTec Product is a digital transformer monitoring and diagnostics device that acts as the central “brain” of the TXpert Ecosystem.
The following versions of Hitachi Energy CoreTec Product suffer from the vulnerabilities:
- CoreTec5 versions up to and including 3.4.0
- CoreTec4 versions up to and including 3.4.0
In one issue, an OS command vulnerability exists in CoreTec product that allows authenticated users with certain roles to execute arbitrary system commands with full control over the device. The vulnerability exists in the configuration daemon’s time synchronization handler, which is responsible for setting the system timezone. When processing timezone configuration updates, the daemon constructs a shell command by concatenating user-supplied input without any sanitization or validation.
CVE-2026-13162 is the case number for the vulnerability, which has a CVSS V3 base score of 7.5. There is also a V4 base score of 7.7.
Memory Pages
Additionally, a vulnerability exists in the IPsec ESP subsystem (esp4) of the Linux kernel used in CoreTec5 that allows a local unprivileged user to escalate privileges to root. The flaw exists in how the kernel handles memory pages when processing ESP encrypted network packets. An attacker can craft a packet that causes the kernel to decrypt data directly into memory pages it does not own, including cached copies of privileged operating system binaries. When one of those binaries executes, the attacker’s injected code runs with root privileges. In CoreTec5, the vulnerable ESP component ends up compiled in kernel as a built-in and is present at boot time allowing a local user to exploit it.
CVE-2026-43284 is the case number for the vulnerability, which has a CVSS V3 base score of 8.8.
The product sees use mainly in the energy sector, and on a global basis.
In terms of mitigations:
For CVE-2026-13162:
- CoreTec5 versions 3.4.0 and prior, update to CoreTec5 version 5.0.0
- CoreTec4 versions 3.4.0 and prior upgrade to CoreTec5 version 5.0.0
For CVE-2026-43284:
- CoreTec5 versions 3.4.0 and prior update to CoreTec5 version 5.0.0
- CoreTec4 versions 3.4.0 and prior no update mentioned
- CoreTec5 versions 3.4.0 and prior update to CoreTec5 version 5.0.0
For additional information and support, contact your product provider or Hitachi Energy service organization.
Best Practices
Recommended security practices and firewall configurations can help protect an industrial control system network from attacks that originate from outside the network.
Such practices include that process control systems end up physically protected from direct access by unauthorized personnel, have no direct connections to the Internet, and remain separate from other networks by means of a firewall system that has a minimal number of ports exposed, and others that have to be evaluated case by case.
Industrial control systems should not be used for Internet surfing, instant messaging, or receiving emails. Portable computers and removable storage media should end up carefully scanned for viruses before they connect to a control system.
Additional information on Industrial Control Systems Cybersecurity Best Practices can be found in the Hitachi Energy’s “Industrial Control Systems Cybersecurity Best Practices” Cybersecurity Notification.