The vulnerabilities are missing authentication for critical function, relative path traversal, missing authorization, incorrect authorization, and download of code without integrity check.
Hitachi Energy RTU500 series is a family of modular Remote Terminal Units (RTUs) designed to collect, process, and send data from the physical power grid to a SCADA (Supervisory Control and Data Acquisition) system.
Hitachi Energy published this cybersecurity advisory in response to the security findings reported by Dragos affecting end-of-life RTU500 CMU firmware version 9.x.
The reported findings relate to legacy RTU500 firmware versions developed according to the cybersecurity requirements, threat landscape, and industry practices that existed at the time of their release.
As cybersecurity threats and security expectations evolved, these end-of-life versions no longer incorporate many of the security controls and hardening measures standard in modern industrial control systems.
Enhanced Security
Over successive RTU500 releases, Hitachi Energy continuously enhanced the security of the product through the introduction of additional security features, protocol hardening, stronger authentication and access controls, encrypted communications, and other security-by-design improvements.
While the findings reported by Dragos do not affect currently supported RTU500 CMU firmware versions, there is a likelihood end-of-life versions 11.x and prior end up affected by these vulnerabilities.
The following versions of Hitachi Energy RTU500 suffer from the vulnerabilities: RTU500 series CMU Firmware versions up to and including 11.x.
In one issue, an authentication bypass vulnerability in the firmware update endpoint of Hitachi Energy RTU500 allows an unauthenticated attacker to upload arbitrary firmware through a crafted POST request. Successful exploitation could allow the attacker to modify device functionality or compromise the integrity or availability of the device.
CVE-2026-8065 is the case number for the vulnerability, which has a CVSS V3 base score of 9.1.
Additionally, there is a directory traversal vulnerability in the file upload functionality of Hitachi Energy RTU500 that allows an unauthenticated attacker to write or overwrite arbitrary files on the device file system. Depending on the files affected, successful exploitation could result in unauthorized modification of device data or disruption of the device’s intended operation.
CVE-2026-8066 is the case number for the vulnerability, which has a CVSS V3 base score of 9.1.
Also, an improper authorization vulnerability in the RTU500’s web application allows an authenticated user to trigger the RTU500 to reboot through the reset endpoint. Successful exploitation could cause temporary device unavailability and disruption of its intended operation.
CVE-2026-8067 is the case number for the vulnerability, which has a CVSS V3 base score of 6.5.
Another Vulnerability
Meanwhile, the WDB target agent debug service in Wind River VxWorks 6.x, 5.x, and earlier, as used on few of the Hitachi Energy RTU500 CMU firmware legacy versions, allows remote attackers to read or modify arbitrary memory locations, perform function calls, or manage tasks via requests to UDP port 17185.
CVE-2010-2965 is the case number for the vulnerability, which has a CVSS V3 base score of 9.8.
Moreover, missing authentication vulnerability in a network service of Hitachi Energy RTU500 allows an unauthenticated remote attacker to execute arbitrary commands using protocol-compliant network traffic. Successful exploitation could result in unauthorized modification of the device or disruption of its intended operation.
CVE-2014-9195 is the case number for the vulnerability, which has a CVSS V3 base score of 8.1.
A download of code without integrity check vulnerability in Hitachi Energy RTU500 allows an unauthenticated remote attacker to modify some or all applications running on the device. Successful exploitation could result in unauthorized modification of device functionality or disruption of its intended operation.
CVE-2023-46143 is the case number for the vulnerability, which has a CVSS V3 base score of 7.5.
The product sees use mainly in the energy sector, and on a global basis.
In terms of mitigations, upgrade to version 12.7.8 or 13.9.1 or latest
Recommendations
Moreover, recommended security practices and firewall configurations can help protect a process control network from attacks that originate from outside the network.
Such practices include that process control systems end up physically protected from direct access by unauthorized personnel, and have no direct connections to the Internet. There also has to be separation from other networks by means of a firewall system that has a minimal number of ports exposed, and others that have to end up evaluated case by case.
Additionally, process control systems should not end up used for Internet surfing, instant messaging, or receiving emails.
Users should scan portable computers and removable storage media for viruses before they connect to a control system.
Furthermore, proper password policies and processes should end up followed.
Additional information on Industrial Control Systems Cybersecurity Best Practices can be found in the Hitachi Energy “Industrial Control Systems Cybersecurity Best Practices” Cybersecurity Notification.