Leveraging these remotely exploitable vulnerabilities, discovered by Hitachi Energy PSIRT, could allow an attacker to tamper with system files, cause a denial of service, or perform a remote man-in-the-middle attack.
The following versions of MACH GWS suffer from the vulnerabilities: Versions 3.0.0.0 to 3.4.0.0.
In one issue, a vulnerability exists in MACH GWS product, which if exploited, could allow a local unauthenticated attacker to tamper a system file resulting in a denial of notify service.
CVE-2025-39201 is the case number for this vulnerability, which has a CVSS v3.1 base score of 6.1. There is also a CVSS v4 base score of 6.9.
Additionally, a vulnerability exists in the IEC 61850 of the MACH GWS product where an IEC 61850-8 crafted message content from IED or remote system can cause a denial of service resulting in disconnection loop.
CVE-2025-39203 is the case number for this vulnerability, which has a CVSS v3.1 base score of 6.5. There is also a CVSS v4 base score of 7.1.
Another Vulnerability
Also, a vulnerability exists in the IEC 61850 in MACH GWS product where the certificate validation of the TLS protocol allows a remote man-in-the-middle attack due to missing proper validation.
CVE-2025-39205 is the case number for this vulnerability, which has a CVSS v3.1 base score of 6.5. There is also a CVSS v4 base score of 7.1.
The product sees use mainly in the energy sector, and on a global basis.
No exploit targets these vulnerabilities. However, an attacker could leverage these low complexity vulnerabilities.
Hitachi Energy recommends users update to Version 3.5 at the earliest.
Hitachi Energy recommends the following security practices and firewall configurations. This way it is possible to protect a process control network from attacks that originate from outside the network. They include ensuring process control systems are physically protected from direct access by unauthorized personnel, have no direct connections to the Internet, and remain separated from other networks by means of a firewall system that has a minimal number of ports exposed, and others that need evaluation on a case by case basis.
Users should not use process control systems for Internet surfing, instant messaging, or receiving emails. Portable computers and removable storage media should end up carefully scanned for viruses before they connect to a control system. Furthermore, users need to employ proper password policies and processes.
Hitachi Energy recommends users deploy the product following the “GWS deployment guideline” document. Users should maintain their systems with products running on supported versions and follow maintenance releases.
For more information, click on the associated Hitachi Energy PSIRT security advisory 8DBD000222 Multiple Vulnerabilities in Hitachi Energy MACH GWS Product.