JTEKT Corporation has a workaround available to handle an improper resource shutdown or release vulnerability in its TOYOPUC products, according to a report with CISA.

Successful exploitation of this remotely exploitable vulnerability, discovered by Younes Dragoni from Nozomi Networks, could allow an unauthorized user to stop Ethernet communications between devices from being established.

The following versions of these TOYOPUC product series suffer from the issue:

TOYOPUC-PC10 Series:

Schneider Bold
  • PC10G-CPU TCC-6353: All versions
  • PC10GE TCC-6464: All versions
  • PC10P TCC-6372: All versions
  • PC10P-DP TCC-6726: All versions
  • PC10P-DP-IO TCC-6752: All versions
  • PC10B-P TCC-6373: All versions
  • PC10B TCC-1021: All versions
  • PC10B-E/C TCU-6521: All versions
  • PC10E TCC-4737: All versions

TOYOPUC-Plus Series:

  • Plus CPU TCC-6740: All versions
  • Plus EX TCU-6741: All versions
  • Plus EX2 TCU-6858: All versions
  • Plus EFR TCU-6743: All versions
  • Plus EFR2 TCU-6859: All versions
  • Plus 2P-EFR TCU-6929: All versions
  • Plus BUS-EX TCU-6900: All versions

TOYOPUC-PC3J/PC2J Series:

  • FL/ET-T-V2H THU-6289: All versions
  • 2PORT-EFR THU-6404: All versions

In the vulnerability, if Ethernet communication of the affected product is left in an open state by an attacker, Ethernet communications cannot be established with other devices, depending on the settings of the link parameters.

CVE-2021-27458 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 7.5.

The product sees use mainly in the critical manufacturing sector, and it sees action on a global basis.

No known public exploits specifically target this vulnerability. However, since the vulnerability has low complexity, an attacker could leverage the issue.

Japan-based JTEKT Corporation recommends users to use the following workaround:

  1. Access the link parameter screen of either “Ethernet” or “Ethernet (32Port)”
  2. Access the Timer setting by clicking on the “Timers” button
  3. Set “Non-Reception timer” to “Enable” in the “Timers” section
  4. After setting the link parameter, connect a computer and a PLC with a USB cable and write the link parameter
  5. After the writing is completed, perform a reset/start or power-on again
  6. After reset/start or power-on, the parameter changes take effect
  7. When “Non-Reception timer” is set to “Enabled,” the connection that was not closed correctly can be reset after the set time has elapsed and a connection can communicate with a device that should be connected

For additional information send an email to JTEKT Corporation.