The furnace pre-heats renewable feedstock, recycled renewable diesel, and hydrogen before subsequent processing. On November 19, at 12:21 a.m., a metal tube ruptured within a reactor charge furnace during a unit startup at the Martinez Renewables facility.
The ruptured tube released hot renewable diesel and hydrogen, resulting in a fire that seriously injured one Marathon employee who suffered third-degree burns to most of his face and body, according to an investigation update from the Chemical Safety and Hazard Investigation Board (CSB).
The incident occurred during the initial startup of a hydrodeoxygenation (HDO) unit, a process unit converted from a diesel hydrotreater unit in the original petroleum refinery. The HDO process catalytically removes oxygen from the renewable feedstock before it ends up processed further in downstream units to make renewable diesel, an alternative to conventional diesel fuel. Marathon repurposed equipment from its original diesel hydrotreater unit, reconfigured the process piping, and introduced new equipment to convert the existing unit into the new HDO unit.
Incident Occurs During Startup
“Like here, many of the incidents that have been investigated by the CSB have occurred during start-ups when conditions at a facility can change quickly,” said CSB Chairperson Steve Owens. “These situations can present a unique set of safety hazards that must be carefully managed and controlled.”
The design of the HDO unit was with a furnace to pre-heat renewable feedstock, recycled renewable diesel, and hydrogen before subsequent processing. Within the furnace, up to eleven fuel-gas fired burners heated the process materials, which flowed through stainless steel tubes inside the furnace. During the HDO conversion project, Marathon installed new, reconfigured tubes in the furnace. Documentation indicates the new tubes consisted of ASTM A312 Grade 321 stainless steel.
The following is a time line of events the CSB found leading up to the incident:
On the night shift of November 18, Marathon was in the process of starting up the HDO unit. Personnel established renewable diesel and hydrogen circulation in the unit and started using the furnace to heat up the process materials.
During the hour leading up to the incident, Marathon operations staff were attending to furnace temperature control issues. Temperature instruments inside the furnace indicated excessive temperatures on the furnace tube surfaces, triggering audio and visual high temperature alarms at 1,100 °F on computer control system screens inside the control room. Minutes before the rupture, all tube temperature indicators were in excess of the high-temperature alarm setpoints, with 8 out of 10 instruments indicating temperatures ranging from approximately 1,490 °F to 1,710 °F.

Surveillance footage of when fire started in the furnace at the renewables facility.
Source: Marathon
Timeline to the Incident
To reduce temperatures within the furnace, Marathon operations staff increased the flow of material through the furnace and directed a field operator to turn off two of the furnace burners.
At the furnace, the field operator closed manual fuel gas valves to turn off two of the four burners that were lit at the time. Around 12:21 a.m., just after the field operator had completed this action, a tube ruptured within the furnace, releasing hot renewable diesel and hydrogen.
The materials released from the furnace and ignited, causing a fire. The field operator suffered serious injuries from the release and fire, suffering third-degree burns to most of his face and body. Despite his severe injuries, he made his way 80 yards from the furnace area to the field operator shelter, where fellow operators discovered him and then air-lifted him to a nearby hospital. The fire was out by 1:15 a.m., and an all-clear was at 2 a.m.
The morning after the incident, Marathon employees discovered a normally closed manual bypass valve upstream of the furnace was open (misaligned), which created a potential flow path around the furnace. The flowmeter intended to monitor diesel flow through the furnace was upstream of the open bypass valve, and was indicating flow at the time of the incident.
Although safety interlocks existed to automatically shut down the furnace during low renewable diesel flow to the furnace and high temperatures downstream of the furnace, none of these conditions ended up detected by the instrumentation, and the interlocks did not activate. Any flow being bypassed around the furnace would have fed back into the process piping upstream of the high temperature safety interlock instrumentation.
Ruptured Tue Release Point
A post-incident examination of the furnace identified the release point as a ruptured tube in the convection section of the furnace. Further investigation of the furnace tubes is ongoing.
The CSB is continuing to gather facts and analyze several key areas, including:
- Ongoing inspection of furnace internal components
- Furnace tube metallurgy and failure mode analysis
- Identification and control of potentially hazardous scenarios
- Relevant facility, corporate, and industry standards
“Our team still has a lot of investigative work to do,” said Investigator-in-Charge Melike Yersiz. “Ultimately, our goal is to identify probable causes of this incident and develop safety recommendations to prevent a similar event from occurring.”
Click here for more on the investigation.