Mitsubishi Electric has a mitigation plan to handle an uncontrolled resource consumption vulnerability in its MELSEC iQ-R Series, according to a report with CISA.
Successful exploitation of this remotely exploitable vulnerability, discovered by Younes Dragoni of Nozomi Networks, may prevent legitimate clients from connecting to an affected product.
The following MELSEC iQ-R series CPU modules suffer from the issue:
- R00/01/02CPU: All versions
- R04/08/16/32/120(EN)CPU: All versions
- R08/16/32/120SFCPU: All versions
- R08/16/32/120PCPU: All versions
- R08/16/32/120PSFCPU: All versions
Due to improper session management, an attacker may prevent legitimate clients from connecting to an affected product by manipulating the link parameter or changing its state. If multiple MELSOFT transmission ports (TCP/IP) are open, the other ports are not affected. Sequence control is not affected by this vulnerability.
CVE-2021-20591 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 5.3.
The product sees use mainly in the critical manufacturing sector, and on a global basis.
No known public exploits specifically target this vulnerability. However, an attacker with low skill level could leverage the low complexity vulnerability.
Mitsubishi Electric recommends the following mitigations:
- Use a firewall, a virtual private network (VPN), etc., to prevent unauthorized access when Internet access is required.
- Use within a LAN and block access from untrusted networks and hosts through firewalls.
- Use the IP filter function to restrict the connectable IP addresses. See MELSEC iQ-R Ethernet User’s Manual (Application) 1.13 Security “IP filter” for more information.
- Use the MELSOFT transmission port (UDP/IP).
- If Port 5007 of the MELSOFT transmission port (TCP/IP) is not used, set b2 to “1” in advance. See MELSEC iQ-R Ethernet User’s Manual (Application) Appendix 3, Buffer Memory for more information.
If this vulnerability ends up exploited, legitimate users can recover by first disabling the port with the forced connection invalidation function and then re-enabling the port. For an example see MELSEC iQ-R Ethernet User’s Manual (Application) Appendix 3, Buffer Memory.
Click on the Mitsubishi Electric advisory for further details.