Mitsubishi Electric has updates available to handle observable timing discrepancy, double free, and access of resource using incompatible type (‘type confusion’) vulnerabilities in multiple Factory Automation products, according to a report with CISA.

Successful exploitation of these remotely exploitable vulnerabilities, which Mitsubishi Electric self-reported, could disclose information in the product or could cause a denial-of-service (DoS) condition.

In one issue, the affected products contain an observable timing discrepancy vulnerability in their RSA decryption implementation. By sending specially crafted packets and performing a Bleichenbacher style attack, an attack method to decrypt ciphertext by observing the behavior when a padding error occurs, an attacker could decrypt the ciphertext and disclose sensitive information.

CVE-2022-4304 is the case number for this vulnerability, which has a CVSS v3.1 base score of 5.9.

In addition, the affected products contain a double free vulnerability when reading a PEM file. An attacker could cause denial-of-service (DoS) on the product by leading a legitimate user to importing a malicious certificate.

Schneider Bold

CVE-2022-4450 is the case number for this vulnerability, which has a CVSS v3.1 base score of 7.5.

Also, the affected products contain a type confusion vulnerability relating to X.400 address processing inside an X.509 GeneralName. An attacker could disclose sensitive information in memory of the product or cause denial-of-service (DoS) on the product by getting to load a specially crafted certificate revocation list (CRL).

CVE-2023-0286 is the case number for this vulnerability, which has a CVSS v3.1 base score of 7.4.

The following Factory Automation products suffer from the issue:

  • GT SoftGOT2000: Versions 1.275M to 1.290C (CVE-2023-0286)
  • OPC UA Data Collector: Versions 1.04E and prior (CVE-2023-0286)
  • MX OPC Server UA (Software packaged with MC Works64): Versions 3.05F and later (Packaged with MC Works64 Version 4.03D and later) (CVE-2022-4304)
  • OPC UA Server Unit: All versions (CVE-2022-4304)
  • FX5-OPC: Versions 1.006 and prior (CVE-2022-4304, CVE-2022-4450)

The product sees use mainly in the critical manufacturing sector, and on a global basis.

No known public exploits target these vulnerabilities. However, an attacker could leverage these low complexity vulnerabilities.

Mitsubishi Electric recommends users update their products to the following versions:

  • GT SoftGOT2000: Version 1.295H or later
  • OPC UA data collector: 1.05F or later
  • MX OPC Server UA: Use recommended mitigations/workarounds
  • OPC UA server unit: Use recommended mitigations/workarounds
  • FX5-OPC: Version 1.010 or later

Mitsubishi Electric recommends users take the following mitigation measures to minimize the risk of exploiting these vulnerabilities:

GT SoftGOT2000 and OPC UA Data Collector: Do not load untrusted certificate revocation lists (CRLs).

MX OPC Server UA: Use within a LAN and block access from untrusted networks and hosts through firewalls. Restrict physical access to the product, as well as to computers and network devices located within the same network as the product. Use a firewall or virtual private network (VPN), etc. to prevent unauthorized access when you must have Internet access.

OPC UA Server Unit: Use within a LAN and block access from untrusted networks and hosts through firewalls. Restrict physical access to the product, as well as to computers and network devices located within the same network as the product. Use a firewall or virtual private network (VPN), etc. to prevent unauthorized access when you must have Internet access. Set a security policy other than ‘None’ in security setting function to prevent unauthorized access. For details on security setting function, please refer to the MELSEC iQ-R OPC UA Server Unit User’s Manual (Application), section 1.1 “OPC UA Server Function.”

FX5-OPC: Use within a LAN and block access from untrusted networks and hosts through firewalls. Restrict physical access to the product, as well as to computers and network devices located within the same network as the product. Use a firewall or virtual private network (VPN), etc. to prevent unauthorized access when you must have Internet access. Use the IP filter function to block access from untrusted hosts. For details on the IP filter function, please refer to the MELSEC iQ-F FX5 OPC UA Module User’s Manual section 4.4 “IP Filter.” Do not import untrusted certificates.

For additional details, click on the Mitsubishi Electric advisory 2023-018.

 

Pin It on Pinterest

Share This