Moxa has fixes available to handle multiple vulnerabilities in its MB3170 series, MB3180 series, MB3270 series, MB3280 series, MB3480 series, and MB3660 series, according to a report with CISA.

The vulnerabilities are stack-based buffer overflow, integer overflow to buffer overflow, cross-site request forgery, use of a broken or risky cryptographic algorithm, information exposure, cleartext transmission of sensitive information, weak password requirements, cleartext storage of sensitive information, and incorrectly specified destination in a communication channel.

Successful exploitation of these remotely exploitable vulnerabilities, discovered by Ilya Karpov and Evgeniy Druzhinin from Rostelecom-Solar, and Maxim Kozhevnikov from Positive Technologies, could crash the device, cause a buffer overflow, allow remote execution of arbitrary code, or allow access to sensitive information.

The vulnerabilities affects the following protocol gateways:

Schneider Bold
  • MB3170 series firmware, Version 4.0 or lower
  • MB3270 series firmware, Version 4.0 or lower
  • MB3180 series firmware, Version 2.0 or lower
  • MB3280 series firmware, Version 3.0 or lower
  • MB3480 series firmware, Version 3.0 or lower
  • MB3660 series firmware, Version 2.2 or lower
  • In one vulnerability, two separate issues cause a buffer overflow in the built-in web server that may allow a remote attacker to initiate a DoS attack and execute arbitrary code.

    CVE-2019-9099 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 9.8.

    In addition, an integer overflow causes unexpected memory allocation that can lead to a buffer overflow.

    CVE-2019-9098 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 7.5.

    Also, a predictable mechanism of generating tokens allows remote attackers to bypass the cross-site request forgery (CSRF) protection mechanism.

    CVE-2019-9102 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 8.8.

    In another issue, a weak cryptographic algorithm with predictable variables may allow sensitive information to be revealed.

    CVE-2019-9095 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 7.5.

    In addition, an attacker can access sensitive information and usernames via the built-in web service without proper authorization.

    CVE-2019-9103 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 5.3.

    Also, sensitive information is transmitted over some web applications in clear text.

    CVE-2019-9101 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 7.5.

    In another case, weak password requirements may allow an attacker to gain access by using brute force.

    CVE-2019-9096 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 9.8.

    In addition, sensitive information is stored in configuration files without encryption, which may allow an attacker to access an administrative account.

    CVE-2019-9104 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 8.2.

    Also, the web service may become temporarily unavailable if an attacker is able to overload the system to cause the service to crash.

    CVE-2019-9097 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 5.3.

    The product sees use mainly in the critical manufacturing, energy, and water and wastewater systems sectors. It also sees action on a global basis.

    No known public exploits specifically target these vulnerabilities. However, an attacker with low skill level could leverage the vulnerabilities.

    Moxa has developed the following solutions to address the vulnerabilities:

  • MB3170 Series: Download the new firmware
  • MB3270 Series: Download the new firmware
  • MB3180 Series: Download the new firmware
  • — Moxa also recommends users follow below instructions to mitigate potential risks:
    Upgrade to the latest firmware and disable HTTP and Telnet communications
    Use Moxa utilities (MGate Manager, NPort Administration Suite Utility) to change device configurations or monitor the device status remotely
    Use a VPN tunnel for a secure and protected connection between the devices and host PC

  • MB3280 Series: Download the new firmware
  • MB3480 Series: Download the new firmware
  • MB3660 Series: Download the new firmware
  • Click on Moxa’s security advisory for more information.

    Pin It on Pinterest

    Share This