As part of the Moore Industries FS Functional Safety Series, the SLA conforms to IEC 61508:2010 standards and received exida certification for use in Safety Instrumented Systems (SIS) for systematic integrity up to SIL 3 and for random integrity up to SIL 2.
The SLA performs as a multiloop logic solver with built-in voting and enhanced math capability typically found in costly and complex safety PLCs.
The 4-wire (line/mains powered) SLA accepts up to four discrete and six analog inputs from a wide array of devices and sensors.
HART data from connected field devices passes through the SLA to its analog outputs enabling connected hosts and asset managers bi-directional communication for continuous monitoring and programming.
Its four relay outputs and up to four discrete contact closure outputs can end up driven by any of 16 internally configured alarms, where individual or multiple alarms can be assigned to each relay or discrete output. Relay and discrete outputs can also be triggered by any input or internal diagnostic fault. Three optional analog outputs allow transmission of any input or internally calculated equation or variable.
The SLA is easily programmable with any FDT compliant host utilizing the SLA’s DTM with simple drop-down menus and checkboxes; no custom or licensed software is required. This ease-of-use functionality includes a powerful equation editor the user can employ to create monitoring, alarming, and control schemes involving simple to complex equations using timers, running min/max functions, prebuilt analog and discrete logic functions and more.

Moore Industries’ SLA Multiloop and Multifunctional Safety Logic Solver and Alarm performs as a multiloop logic solver with built-in voting and enhanced math capability typically found in costly and complex safety PLCs.
The SLA features secure programming and communications with security jumpers that can end up set to prevent unauthorized reprogramming and ensure read-only communications through the Ethernet and MODBUS ports. It supports MODBUS/TCP and MODBUS RTU industrial protocols and has an embedded read-only web server that allows all inputs, outputs, internal variables and various other parameters to be read with a simple web browser.
The SLA is exida certified to IEC 61508:2010 for systematic integrity up to SIL 3 and for random integrity up to SIL 2. This means the SLA is approved for single use in safety applications up to SIL 2 and in a redundant architecture (1oo2, 2oo3, etc.) up to SIL 3. FMEDA certified safety data is available upon request allowing a functional safety practitioner to access the FMEDA data on the SLA to determine the SLA’s applicability in specific safety-related applications.
“The IEC 61508 certified SLA finally provides safety practitioners with a cost effective, powerful yet easy to employ multichannel safety logic solver that fills the large functionality gap between high-end Safety PLCs and the limited capabilities of Single Loop Logic Solvers within Safety Instrumented Systems,” said Scott Saunders, Moore Industries president and chief executive.
Click here to view the available models. Click here to download the data sheet.