Successful exploitation of this remotely exploitable vulnerability, discovered by researchers of Titanium Industrial Security, could allow an attacker to reboot the device remotely. The following versions of CompactRIO, a real-time embedded industrial controller, suffer from the issue: Driver versions prior to 20.5.
In the vulnerability, incorrect permissions are set by default for an API entry-point of a specific service, allowing a non-authenticated user to trigger a function that could reboot the device remotely.
CVE-2020-25191 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 7.5.
The product sees use mainly in the critical manufacturing sector. It also sees action on a global basis.
No known public exploits specifically target this vulnerability. However, an attacker with low skill level could leverage the vulnerability.
NI recommends the following steps for mitigation:
- Download the NI CompactRIO 20.5 Driver.
- Install the driver on host computer.
- Update the firmware on CompactRIO controllers to v8.5 or higher. Refer to “Upgrading Firmware on my NI Linux Real-Time Device” for directions on how to update the firmware on current controllers. Updating the firmware patches the Safe Mode where defaults end up loaded.
- Format the target to apply the new safemode default permissions. Refer to “How to Restore LabVIEW RT Target to Factory Default Configuration” for directions on how to format and reinstall software on target.
- Repeat Steps 3 and 4 for each affected CompactRIO target.