By Mark Carrigan
After the Chemical Safety Board (CSB) filed an update on the January 28, 2021 tragedy at the Foundation Food Group (FFG) poultry facility in Gainesville, Georgia, that left six workers dead and at least 12 others injured, it just pointed out the stark reminder of the danger that nitrogen poses when leaked into a confined space, causing a drop in oxygen concentration that can lead to dire cosequences.
Once released, the liquid nitrogen quickly vaporized, expanded, and accumulated inside a partially enclosed room within a building. FFG used liquid nitrogen for the freezing of cooked poultry products.
Nitrogen is a colorless, odorless, non-flammable, non-toxic gas that is abundant in the air.
The events that unfolded are unfortunately very similar to other incidents that have led to a loss of life and typically take place as follows:
- A leak takes place in a confined area where people regularly work. This leak usually takes place while no one is in the room and goes unobserved.
- The leak is typically liquid nitrogen (or another highly cooled asphyxiant) that expands rapidly as it vaporizes, quickly reducing the oxygen level to an unsafe condition.
- A person enters the confined area, completely unaware of the danger. Nitrogen is colorless and odorless (it comprises 80 percent of the air we breathe). It is only unsafe when displacing oxygen to unsafe levels.
- After a short period of time the person becomes incapacitated, losing consciousness. In extreme conditions a person can lose consciousness within a few breaths if the oxygen levels are particularly low. Your lungs work via osmosis – oxygen moves in the direction from highest concentration to lowest concentration. When breathing normal air, oxygen moves from the air to your lungs (where the concentration is less). In the case where oxygen concentration is particularly low (less than 10 percent), this atmosphere will actually remove oxygen from your body when breathing. As a result you can lose consciousness far quicker than by just holding your breath.
- A second person comes along, observes that the first person is in distress, and enters the unsafe space with a desire to help. This person quickly succumbs. More people may fall prey until the danger is recognized.
- The danger is finally realized and properly equipped personnel, with oxygen breathing systems, enter the space to render assistance.
That was exactly what occurred in the Foundation Food Group incident when workers started processing chicken on Line 4 between 7 and 7:30 a.m. Workers stopped processing chicken at 8:14 a.m. because the freezer was not properly freezing the chicken product. Line 4 production workers went on a break while maintenance staff worked to correct the issue.
When Line 4 workers returned from their break, they saw their line had not yet restarted. After the line workers waited for over an hour, one of them entered the freezer room through the elevated opening to check on the maintenance workers around 9:30 or 9:40 a.m. The line worker saw a white cloud approximately four feet high filling the room and one of the maintenance workers lying unconscious on the ground next to the freezer. The line worker exited the freezer room and notified the other workers and supervisors.
Several of these employees that helped with the rescue efforts ended up seriously or fatally injured from exposure to the nitrogen vapors.
While the CSB investigation is ongoing, there is no doubt this was a great tragedy shows oxygen deficient atmospheres can claim multiple lives as they victimize additional people who are only trying to help.
Companies that utilize liquid nitrogen or other potential asphyxiation hazards should take a proactive approach to identify the hazardous and implement a program to reduce the likelihood of a catastrophic event.
Programs to reduce this risk should include:
- Identify areas where a leak could allow an asphyxiant to enter into a confined space – pay particular attention to where valves and other connections are located that have the potential to fail and cause a leak
- Install oxygen monitors in these high-risk areas with indicators both within and entry to points to these locations to warn people of hazardous conditions
- Install oxygen breathing equipment near these entry points, clearly marked, so that first responders have quick access during an emergency situation
- Provide regular training to operations personnel on the potential hazards and emergency response procedures
Mark Carrigan is senior vice president of process safety & OT cybersecurity at Hexagon.