Rockwell Automation revised its software to handle deserialization of untrusted data, path traversal, and improper input validation vulnerabilities in its Connected Components Workbench, according to a report with CISA.

Successful exploitation of these remotely exploitable vulnerabilities, discovered by Mashav Sapir of Claroty, may allow remote code execution, authentication bypass, or privilege escalation.

Rockwell reports these vulnerabilities affect the following Connected Components Workbench versions: V12.00.00 and prior.

In one issue, Connected Components Workbench does not limit the objects that can be deserialized.

This vulnerability allows attackers to craft a malicious serialized object that, if opened by a local user in Connected Components Workbench, may result in remote code execution. This vulnerability requires user interaction to be successfully exploited.

Schneider Bold

CVE-2021-27475 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 8.6.

In addition, the parsing mechanism that processes certain file types does not provide input sanitization for file paths. This may allow an attacker to craft malicious files that, when opened by Connected Components Workbench, can traverse the file system. If successfully exploited, an attacker could overwrite existing files and create additional files with the same permissions of the Connected Components Workbench software. User interaction is required for this exploit to be successful.

CVE-2021-27471 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 7.7.

Also, Connected Components Workbench does not sanitize paths specified within the .ccwarc archive file during extraction. This type of vulnerability is also commonly referred to as a Zip Slip. A local, authenticated attacker can create a malicious .ccwarc archive file that, when opened by Connected Components Workbench, will allow the attacker to gain the privileges of the software. If the software is running at SYSTEM level, the attacker will gain admin level privileges. User interaction is required for this exploit to be successful.

CVE-2021-27473 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 6.1.

The product sees use in the commercial facilities, defense industrial base, energy, and government facilities sectors. It also sees action on a global basis.

No known public exploits specifically target these vulnerabilities. However, an attacker with low skill level could leverage the low complexity issues.

Rockwell recommends users of the affected software update to an available software revision (Connected Components Workbench v13.00.00 or later) that addresses the associated risk. Users who are unable to update are directed toward risk mitigation strategies provided below, and are encouraged, when possible, to combine these with Rockwell’s general security guidelines to employ multiple strategies simultaneously.

  • If upgrade is not possible, Rockwell Automation recommends deploying the following mitigations:
  • Run Connected Components Workbench as a User, not as an Administrator, to minimize the impact of malicious code on the infected system.
  • Do not open untrusted .ccwarc, files with Connected Components Workbench. Employ training and awareness programs to educate users on the warning signs of a phishing or social engineering attack.
  • Use of Microsoft AppLocker or other similar allow list applications can help mitigate risk. Information on using AppLocker with Rockwell Automation products is available at KnowledgeBase Article QA17329 (login required). 
  • Ensure the least-privilege user principle is followed, and user/service account access to shared resources (such as a database) is only granted with a minimum number of rights as needed.

For more information, click on the industrial security advisory from Rockwell Automation.

Pin It on Pinterest

Share This