Rockwell Automation has patches available to handle improper input validation, path traversal, and unrestricted upload of file with dangerous type vulnerabilities in its FactoryTalk Linx Software, according to a report with CISA.

Successful exploitation of these remotely exploitable vulnerabilities, discovered by Sharon Brizinov and Amir Preminger (VP Research) of Claroty, could allow an attacker to cause a denial-of-service condition, obtain remote code execution, and read sensitive information.

The following products suffer from the issues:

  • FactoryTalk Linx versions 6.00, 6.10, and 6.11

The following products that utilize FactoryTalk Linx Software also end up affected:

Schneider Bold
  • Connected Components Workbench: Version 12 and prior
  • ControlFLASH: Version 14 and later
  • ControlFLASH Plus: Version 1 and later
  • FactoryTalk Asset Centre: Version 9 and later
  • FactoryTalk Linx CommDTM: Version 1 and later
  • Studio 5000 Launcher: Version 31 and later
  • Studio 5000 Logix Designer software: Version 32 and prior

In one issue, an exposed API call allows users to provide files to end up processed without sanitation. This may allow an attacker to specify a filename to execute unauthorized code and modify files or data.

CVE-2020-11999 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 9.6.

In addition, the parsing mechanism that processes certain file types does not provide input sanitation. This may allow an attacker to use specially crafted files to traverse the file system and modify or expose sensitive data or execute arbitrary code.

CVE-2020-12001 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 9.6.

Also, an exposed API call allows users to provide files to end up processed without sanitation. This may allow an attacker to use specially crafted requests to traverse the file system and expose sensitive data on the local hard drive.

CVE-2020-12003 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 7.5.

In another issue, a vulnerability exists in the communication function that enables users to upload EDS files by FactoryTalk Linx. This may allow an attacker to upload a file with bad compression, consuming all the available CPU resources, leading to a denial-of-service condition.

CVE-2020-12005 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 7.5.

The product sees use in the critical manufacturing, energy, and water and wastewater systems sectors. It also sees action on a global basis.

No known public exploits specifically target these vulnerabilities. However, an attacker with low skill level could leverage the vulnerabilities.

Rockwell Automation recommends users apply these patches by following instructions in knowledgebase articles below:

  • Patch Roll-up for CPR9 SRx (Login Required)
  • FactoryTalk Linx/Services patch RAID# 1124820 (Login Required)
  • FactoryTalk Linx patch RAID# 1126433 (Login Required)
  • Network-based vulnerability mitigations for embedded products:

  • Block all traffic to EtherNet/IP or other CIP protocol-based devices from outside the manufacturing zone by blocking or restricting access to TCP Ports 2222, 7153, and UDP Port 44818 using proper network infrastructure controls, such as firewalls, UTM devices, or other security appliances. For more information on TCP/UDP ports used by Rockwell Automation products, see Knowledgebase Article ID 898270.
  • General mitigations:

  • Locate control system networks and devices behind firewalls and isolate them from the business network.
  • When remote access is required, use secure methods, such as virtual private networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.
  • For more information, please refer to Rockwell Automation’s security advisory: 54102-Industrial Security Advisory Index.