Rockwell Automation has software updates to handle improper input validation and heap-based buffer overflow vulnerabilities in its FactoryTalk Linx, according to a report with CISA.

Successful exploitation of these remotely exploitable vulnerabilities, discovered by Sharon Brizinov of Claroty, could allow a denial-of-service condition, remote code execution, or leak information that could end up used to bypass address space layout randomization (ASLR).

The following versions of FactoryTalk Linx suffer from the issues: FactoryTalk Linx: Version 6.11 and prior.

In one vulnerability, a flaw exists in the Ingress/Egress checks routine of FactoryTalk Linx. This vulnerability could allow a remote, unauthenticated attacker to specifically craft a malicious packet resulting in a denial-of-service condition on the device.

CVE-2020-27253 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 8.6.

Schneider Bold

In addition, a heap overflow vulnerability exists within FactoryTalk Linx. This vulnerability could allow a remote, unauthenticated attacker to send malicious port ranges, which could result in remote code execution.

CVE-2020-27251 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 9.8.

Also, a heap overflow vulnerability exists within FactoryTalk Linx. This vulnerability could allow a remote, unauthenticated attacker to send malicious set attribute requests, which could result in the leaking of sensitive information. This information disclosure could lead to the bypass of address space layout randomization (ASLR).

CVE-2020-27255 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 5.3.

The product sees action in the critical manufacturing, energy, and water and wastewater systems sectors. It also sees action on a global basis.

No known public exploits specifically target these vulnerabilities. However, an attacker with low skill level could leverage the vulnerabilities.

Rockwell Automation recommends users of the affected FactoryTalk Linx update to an available software revision that addresses the associated risk.

FactoryTalk Linx v6.10/6.11 (see Patch Answer ID 1126433).  Additionally, the user could move to v6.20, which is available on PCDC (login required).

  • Rockwell Automation recommends users who are unable to update should follow these mitigations or workarounds to further reduce risk. Users should, when possible, combine these with general security guidelines to employ multiple strategies simultaneously:
  • Run all software as “user” (not as “administrator”) to minimize the impact of malicious code on the infected system.
  • Use of Microsoft AppLocker or other similar whitelisting application can help mitigate risk. Information on using AppLocker with Rockwell Automation products is available at Knowledgebase Article ID 546989 (login required).
  • Confirm the least-privilege user principle ends up followed, and user/service account access to shared resources (such as a database) ends up  granted with a minimum amount of rights.
  • Use trusted software, software patches, antivirus/antimalware programs, and interact only with trusted websites and attachments.
  • Minimize network exposure for all control system devices and/or systems and confirm they are not accessible from the Internet. For further information about the risks of unprotected Internet-accessible control systems, see Knowledgebase Article ID 494865 (login required).
  • Locate control system networks and devices behind firewalls and isolate them from the business network.
  • When remote access ends up required, use secure methods, such as virtual private networks (VPNs), recognizing VPNs may have vulnerabilities and users should update them to the most current version available.

For more information refer to Rockwell’s Industrial Security Advisory ID 1128684 (login required).