Schneider Electric has mitigations available to handle multiple vulnerabilities in its Modicon M221 Programmable Logic Controller, according to a report with CISA.

The vulnerabilities include inadequate encryption strength, small space of random values, missing encryption of sensitive data, exposure of sensitive information, use of a one-way hash with a predictable salt.

Successful exploitation of these vulnerabilities, which are exploitable from an adjacent network, could allow an attacker to take control over the PLC and gain unauthorized access, which could result in exposure of sensitive information. Yehuda Anikster and Rei Henigman of Claroty, and Seok Min Lim and Bryon Kaan of Trustwave reported these vulnerabilities to Schneider Electric.

These vulnerabilities affect the following Modicon products: M221, all versions.

In one issue, an inadequate encryption strength vulnerability exists that could allow the attacker to break the encryption key when the attacker has captured the traffic between EcoStruxure Machine – Basic software and Modicon M221 controller.

Schneider Bold

CVE-2020-7565 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 7.1.

In addition, a small space of random values vulnerability exists that could allow the attacker to break the encryption keys when the attacker has captured the traffic between EcoStruxure Machine – Basic software and Modicon M221 controller.

CVE-2020-7566 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 7.1.

Also, a missing encryption of sensitive data vulnerability exists that could allow the attacker to find the password hash when the attacker captured the traffic between EcoStruxure Machine – Basic software and Modicon M221 controller and has broken the encryption keys.

CVE-2020-7567 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 7.1.

In another issue, an exposure of sensitive information to an unauthorized actor vulnerability exists that could allow non-sensitive information disclosure when the attacker has captured the traffic between EcoStruxure Machine – Basic software and Modicon M221 controller.

CVE-2020-7568 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 3.1.

In addition, a use of a one-way hash with a predictable salt vulnerability exists that could allow the attacker to pre-compute the hash value using a dictionary attack, effectively disabling the protection that an unpredictable salt would provide.

CVE-2020-28214 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 3.3.

The product sees use in the commercial facilities, energy, food and agriculture, government facilities, transportation systems, and water and wastewater systems sectors. It also sees action on a global basis.

No known public exploits specifically target these vulnerabilities. High skill level is needed to exploit.

Schneider recommends users to apply the following mitigations to help reduce the risk of exploit:

  • Set up network segmentation and implement a firewall to block all unauthorized access to Port 502/TCP.

Within the Modicon M221 application, the user must:

  • Disable all unused protocols, especially programming protocol, as described in section “Configuring Ethernet Network” of EcoStruxure Machine Expert – Basic online help for the M221 PLC. This action will prevent unintended remote programming access.
  • Set a password to protect the project.
  • Set a password for read access on the controller.
  • Set a different password for write access on the controller.

Schneider recommends following industry cybersecurity best practices:

  • Locate control and safety system networks and remote devices behind firewalls and isolate them from the business network.
  • Install physical controls so no unauthorized personnel can access industrial control and safety systems, components, peripheral equipment, and networks.
  • Place all controllers in locked cabinets and never leave them in the “Program” mode.
  • Never connect programming software to any network other than the specific network meant for the devices.
  • Scan all methods of mobile data exchange with the isolated network (e.g., CDs, USB drives, etc.) before use in the terminals or any node connected to these networks.
  • Never allow mobile devices that connected to any other network, besides the intended network, to connect to the safety or control networks without proper sanitation.
  • Minimize network exposure for all control system devices and systems and ensure they are not accessible from the Internet.
  • When you require remote access, use secure methods such as virtual private networks (VPNs). Recognize that VPNs may have vulnerabilities and should undergo updates to the most current version available. Also, understand that VPNs are only as secure as the connected devices.

For more information refer to the Schneider Electric Recommended Cybersecurity Best Practices document. 

Refer to Schneider Electric’s security bulletin SEVD-2020-315-05 for specific mitigation details. 

Pin It on Pinterest