Siemens has some updates available to handle uncontrolled recursion and buffer access with incorrect length value vulnerabilities in its SIMATIC and SIPLUS products, according to a report with CISA.

Successful exploitation of these remotely exploitable vulnerabilities, which Siemens self-reported, could allow an unauthorized attacker with network access to the web server to perform a denial-of-service attack.

In one issue, the affected products do not handle HTTP(S) requests to the web server correctly. This could allow an attacker to exhaust system resources and create a denial-of-service condition for the device.

CVE-2022-47374 is the case number for this vulnerability, which has a CVSS v3 base score of 7.5.

In addition, the affected products do not handle long file names correctly. This could allow an attacker to create a buffer overflow and create a denial-of-service condition for the device.

Schneider Bold

CVE-2022-47375 is the case number for this vulnerability, which has a CVSS v3 base score of 7.5.

The following products suffer from the vulnerabilities:

  • SIMATIC S7-400 CPU 412-2 PN V7 (6ES7412-2EK07-0AB0): All versions
  • SIMATIC S7-400 CPU 414-3 PN/DP V7 (6ES7414-3EM07-0AB0): All versions
  • SIMATIC S7-400 CPU 414F-3 PN/DP V7 (6ES7414-3FM07-0AB0): All versions
  • SIMATIC S7-400 CPU 416-3 PN/DP V7 (6ES7416-3ES07-0AB0): All versions
  • SIMATIC S7-400 CPU 416F-3 PN/DP V7 (6ES7416-3FS07-0AB0): All versions
  • SIMATIC PC-Station Plus: All versions
  • SINAMICS S120 (incl. SIPLUS variants): All versions prior to SP3 HF15
  • SIPLUS S7-400 CPU 414-3 PN/DP V7 (6AG1414-3EM07-7AB0): All versions
  • SIPLUS S7-400 CPU 416-3 PN/DP V7 (6AG1416-3ES07-7AB0): All versions

The product sees use in multiple industrial sectors, and on a global basis.

No known public exploits target these vulnerabilities. However, an attacker could leverage these low complexity vulnerabilities.

Siemens recommends updating the following products to the latest version where available:
SINAMICS S120 (incl. SIPLUS variants): Update to V5.2 SP3 HF15 or later version 

Siemens has the following workarounds and mitigations users can apply to reduce risk:

  • Disable the web server of the affected system
  • Restrict access to webserver for trusted users only

As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens’ operational guidelines for industrial security and following recommendations in the product manuals.

For more information see the associated Siemens security advisory SSA-892915.