Siemens has updates available to handle multiple vulnerabilities in its LOGO! 8 BM, according to a report with CISA.

The vulnerabilities are missing authentication for critical function, use of hard-coded cryptographic key, use of a broken or risky cryptographic algorithm, and insufficiently protected credentials. Successful exploitation of these remotely exploitable vulnerabilities, discovered by Thomas Meesters from cirosec GmbH, Tobias Gebhardt, and Max Bäumler, could allow an attacker the ability to make configuration and password changes, capture device keys, access confidential information, and gain full control of the device.

The vulnerabilities affect the following LOGO! products:

  • LOGO! 8 BM (incl. SIPLUS variants): All versions prior to 8.3
  • LOGO! Soft Comfort: All versions prior to 8.3 (only affected by CVE-2020-25231, CVE-2020-25234)

In one issue, an attacker who has access to a specific service may gain complete access to all services without authorization.

Schneider Bold

CVE-2020-25228 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 9.8.

In addition, an attacker could execute replay attacks due to the usage of a static key, which may allow unauthorized password or configuration change on any affected device.

CVE-2020-25229 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 8.1.

Also, an attacker can use an outdated cipher mode, which may allow the extraction of the encryption key from captured communication with the device.

CVE-2020-25230 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 5.9.

In another issue, an attacker could use the affected device’s static key to decrypt program data, which may allow extraction of confidential information from protected program files.

CVE-2020-25231 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 6.2.

In addition, an attacker could extract the communication key used when communicating with an affected device, which may allow confidential information disclosure.

CVE-2020-25232 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 5.9.

Also, an attacker may obtain the private RSA key used for encrypting communication with the device, which may allow confidential information disclosure.

CVE-2020-25233 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 6.2.

In another issue, an attacker could reverse engineer the user-defined functions directly from stored program files.

CVE-2020-25234 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 7.7.

In addition, an attacker with access to network traffic could derive valid logins, which may allow confidential information disclosure.

CVE-2020-25235 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 5.9.

The product sees use in the commercial facilities and transportation systems sectors. It also sees action on a global basis.

No known public exploits specifically target these vulnerabilities. However, an attacker with low skill level could leverage the vulnerabilities.

Siemens s released updates for the affected products and recommends users update to the latest versions:

  • LOGO! 8 BM (incl. SIPLUS variants): Update to v8.3; A new hardware version is required in order to update
  • LOGO! Soft Comfort: Update to v8.3 

Siemens identified the following specific workarounds and mitigations users can apply to reduce the risk:

  1. Protect access to Port 10005/TCP
  2. Apply defense-in-depth concept, including protection concept outlined in the system manual

As a general security measure, Siemens strongly recommends users protect network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends users configure the environment according to Siemens’ operational guidelines for Industrial Security and to follow the recommendations in the product manuals.

Click here for additional information on Industrial Security by Siemens.

For more information, click on Siemens Security Advisory SSA-480824.

Pin It on Pinterest

Share This