Siemens has an update available to handle a cross-site scripting vulnerability in its SICAM A8000, according to a report with CISA.

Successful exploitation of this remotely exploitable vulnerability, discovered by Emma Good from KTH Royal Institute of Technology, could compromise the confidentiality, integrity, and availability of the web application. The following versions of SICAM A8000 RTUs suffer from the issue: SICAM WEB firmware, all versions prior to C05.30.

In the vulnerability, the login screen does not sufficiently sanitize input, which enables an attacker to generate specially crafted log messages. If an unsuspecting user views the log messages via a web browser, these log messages might end up interpreted and executed as code by the web application.

This cross-site scripting (XSS) vulnerability might compromise the confidentiality, integrity, and availability of the web application.

Schneider Bold

CVE-2020-15781 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 8.3.

The product sees use mainly in the energy sector, and it sees action on a global basis.
No known public exploits specifically target this vulnerability. High skill level is needed to exploit.

Siemens recommends users update to the latest version, v05.30. Siemens also recommends users: Disable SICAM WEB feature on the device through the SICAM Device Manager software to mitigate the vulnerability.

As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends configuring the environment according to the Siemens operational guidelines for Industrial Security and following the recommendations in the product manuals.

For additional information, click on Siemens Security Advisory SSA-370042.