Siemens has updates available for an uncaught exception vulnerability in its SIMATIC Controller Web Servers, according to a report with CISA.
Successful exploitation of this remotely exploitable vulnerability, which Siemens self-reported, could allow an attacker to cause a denial-of-service condition.
Siemens reports the vulnerability affects the web server of the following SIMATIC controllers:
- SIMATIC ET 200SP Open Controller (incl. SIPLUS variants): Version 20.8
- SIMATIC S7-1500 Software Controller: Version 20.8
In the vulnerability, an attacker can send a specially crafted HTTP request to the products web server, which may cause a denial-of-service condition.
CVE-2020-15796 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 5.3.
The product sees use mainly in the critical manufacturing sector, and on a global basis.
No known public exploits specifically target this vulnerability. However, an attacker with low skill level could leverage the vulnerability.
Siemens released updates for the affected products and recommends updating to the latest version:
- SIMATIC ET 200SP Open Controller (incl. SIPLUS variants): Update to v21.8Â
- SIMATIC S7-1500 Software Controller: Update to v21.8Â
Siemens said if the PC Station web server does not restart automatically, a Windows reboot is required. This can happen while the control system is running as the PLC control functionality will not end up affected.
As a general security measure, Siemens recommends users protect network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends users configure the environment according to Siemens’ operational guidelines for industrial security and follow the recommendations in the product manuals.
Click here for more information on Siemens Security Advisory SSA-700697.