Siemens has updates available to handle an active debug code vulnerability in its TIM 3V-IE and 4R-IE Family Devices, according to a report from CISA.
Successful exploitation of this remotely exploitable vulnerability, which Siemens self-reported, could allow an unauthenticated attacker with network access to gain full control over the device.
The following versions of TIM communication modules for SIMATIC S7-300 and S7-400 devices suffer from the issue:
- TIM 3V-IE (incl. SIPLUS NET variants): all versions prior to v2.8
- TIM 3V-IE Advanced (incl. SIPLUS NET variants): all versions prior to v2.8
- TIM 3V-IE DNP3 (incl. SIPLUS NET variants): all versions prior to v3.3
- TIM 4R-IE (incl. SIPLUS NET variants): all versions prior to v2.8
- TIM 4R-IE DNP3 (incl. SIPLUS NET variants): all versions prior to v3.3
In the vulnerability, the affected versions contain an open debug port that is available under specific conditions. The vulnerability is only available if the IP address is configured to 192.168.1.2. If available, the debug port could be exploited by an attacker with network access to the device. No user interaction is required to exploit this vulnerability. The vulnerability impacts confidentiality, integrity, and availability of the affected device.
CVE-2019-10939 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 9.0.
The product sees use in the chemical, critical manufacturing, energy, food and agriculture, and water and wastewater systems sectors. It also sees action on a global basis.
No known public exploits specifically target this vulnerability. High skill level is needed to exploit.
Siemens released updates for the affected products and recommends users update to the new version.
- TIM 3V-IE (incl. SIPLUS NET variants) and TIM 3V-IE Advanced (incl. SIPLUS NET variants): Update to v2.8
- TIM 3V-IE DNP3 (incl. SIPLUS NET variants): Update to v3.3
- TIM 4R-IE (incl. SIPLUS NET variants): Update to v2.8
- TIM 4R-IE DNP3 (incl. SIPLUS NET variants): Update to v3.3
Siemens identified the following specific workarounds and mitigations users can apply to reduce the risk:
- Set the IP of the device to anything other than 192.168.1.2
- Limit access to Port 17185/UDP of an affected device (e.g., cell-protection firewall or corporate firewall) to reduce the risk
As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens’ operational guidelines for industrial security and following the recommendations in the product manuals.
Click here for additional information on industrial security by Siemens.
For more information on this vulnerability and more detailed mitigation instructions, please see Siemens security advisory SSA-359303.