Siemens has updates available to take care of heap-based buffer overflow, NULL pointer dereference, and classic buffer overflow vulnerabilities in its SIMATIC ITC Industrial Thin Clients, SIMATIC WinCC Runtime Advanced/Professional, SIMATIC HMI Panels, and its SIPLUS extreme products, according to a report with CISA.

Successful exploitation of these remotely exploitable vulnerabilities in the affected products could allow remote code execution and denial-of-service (DoS) attacks under certain conditions. The vulnerabilities are part of a Kaspersky report.

Vulnerabilities in TightVNC (v1.X), a remote-control software package, affect the following Siemens products:

  • SIMATIC HMI Comfort Outdoor Panels 7” and 15” (including SIPLUS variants): All versions prior to Version 16 update 3
  • SIMATIC HMI Comfort Panel 4” to 22” (including SIPLUS variants): All versions prior to Version 16 update 3
  • SIMATIC HMI KTP Mobile Panels KTP400F, KTP700, KTP700F, KTP900 and KTP900F: All versions prior to Version 16 update 3
  • SIMATIC ITC1500 v3.1: All versions
  • SIMATIC ITC1500 v3.1 PRO: All versions
  • SIMATIC ITC1900 v3.1: All versions
  • SIMATIC ITC1900 v3.1 Pro: All versions
  • SIMATIC ITC2200 v3.1: All versions
  • SIMATIC ITC2200 v3.1 PRO: All versions
  • SIMATIC WinCC Runtime Advanced: All versions prior to Version 16 update 3
  • SIMATIC WinCC Runtime Professional: All version prior to Version 16 update 3

In one vulnerability, TightVNC code Version 1.3.10 contains a heap buffer overflow in rfbServerCutText handler, which can potentially result in code execution. The attack appears to be exploitable via network connectivity.

CVE-2019-15678 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 9.8.

Schneider Bold

In addition, TightVNC code Version 1.3.10 contains a heap buffer overflow in InitialiseRFBConnection function, which can potentially result in code execution. This attack appears to be exploitable via network connectivity.

CVE-2019-15679 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 9.8.

Also, TightVNC code Version 1.3.10 contains a null pointer dereference in HandleZlibBPP function, which could result in a denial-of-service. This attack appears to be exploitable via network connectivity.

CVE-2019-15680 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 7.5.

In another issue, TightVNC code Version 1.3.10 contains a global buffer overflow in HandleCoRREBBP macro function, which can potentially result in code execution. This appears to be exploitable via network connectivity.

CVE-2019-8287 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 9.8.

The product sees use in the chemical, critical manufacturing, energy, food and agriculture, and water and wastewater systems sectors. It also sees action on a global basis.

No known public exploits specifically target these vulnerabilities. However, an attacker with low skill level could leverage the vulnerabilities.

Siemens released updates for several affected products, is working on updates for the remaining affected products and recommends specific countermeasures until fixes are available:
SIMATIC HMI Comfort Outdoor Panels: Update SIMATIC WinCC (TIA Portal) to v16 update 3 or newer, and then update panel to v16 update 3 or newer SIMATIC HMI Comfort Panels: Update SIMATIC WinCC (TIA Portal) to v16 update 3 or newer, and then update panel to v16 update 3 or newer SIMATIC HMI KTP Mobile Panels: Update SIMATIC WinCC (TIA Portal) to v16 update 3 or newer, and then update panel to v16 update 3 or newer SIMATIC WinCC Runtime Advanced: Update to v16 update 3 or newer 
SIMATIC WinCC Runtime Professional: Update to v16 update 3 or newer 

Siemens recommends users restrict access to the device to the internal or VPN network and to trusted IP addresses only.

As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends configuring the environment according to the Siemens operational guidelines for industrial security and following the recommendations in the product manuals. 

For additional information, click on Siemens Security Advisory SSA-478893.

For further inquiries on security vulnerabilities in Siemens products and solutions, contact Siemens ProductCERT.