Siemens has workarounds and mitigations to take care of a business logic errors vulnerability in its SIMOTICS, Desigo, APOGEE, and TALON, according to a report with CISA.
Successful exploitation of this vulnerability, which is exploitable from an adjacent network, could allow an attacker to affect the availability and integrity of the device.
The vulnerability, which Siemens self-reported, affects the following products and versions:
- APOGEE MEC/MBC/PXC (P2): All versions prior to 2.8.2
- APOGEE PXC Series (BACnet): All versions, 3.0 and newer
- APOGEE PCX Series (P2): All versions, 2.8.2 and newer
- Desigo PXC (Power PC): All versions, 2.3x and newer
- Desigo PXM20 (Power PC): All versions, 2.3x and newer
- SIMOTICS CONNECT 400: All versions prior to 0.3.0.330
- TALON TC Series (BACnet): All versions, 3.0 and newer
In the vulnerability, the affected products could allow an attacker to change the IP address of the device to an invalid value. This may allow an attacker to make device configuration changes and affect its availability.
CVE-2019-13939 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 7.1.
The products see use in the chemical, critical manufacturing, energy, food and agriculture, and water and wastewater systems sectors. They also see action on a global basis.
No known public exploits specifically target this vulnerability. However, an attacker with low skill level could leverage the vulnerability.
Siemens recommends the following mitigations and workarounds for the following products:
- Disable the DHCP client and use static IP address configuration instead (Note the DHCP client is disabled by default on APOGEE/TALON and Desigo products)
- APOGEE MEC, MBC, PXC: Use static IP address configuration
- APOGEE PXC Series, TALON TC Series, and Desigo products: If using static IP address is not possible, contact a Siemens support office
- SIMOTICS CONNECT 400: industrial security by Siemens.
For more information see Siemens Security Advisory SSA-162506.