Siemens created patches to handle a code injection vulnerability in its Desigo CC, according to a report with CISA.

Successful exploitation of this remotely exploitable vulnerability, which Siemens self-reported, could allow an attacker to gain remote code execution on the server with SYSTEM privileges.

The following Siemens products and versions suffer from the issue:

  • Desigo CC: Versions 3.x and 4.x
  • Desigo CC Compact: Versions 3.x and 4.x

In the vulnerability, affected applications are delivered with a third-party component that contains a remote code execution vulnerability if the advanced reporting engine is enabled.

Schneider Bold

CVE-2020-10055 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 9.8.

The product sees use mainly in the commercial facilities and government facilities sectors. It also sees action on a global basis.

No known public exploits specifically target this vulnerability. However, an attacker with low skill level could leverage the vulnerability.

Siemens released patches for the affected products and recommends specific countermeasures for unpatched systems:

Siemens identified the following specific workarounds and mitigations users can apply to reduce the risk:

  • If the advanced reporting extension module is already installed, apply the patch provided through Siemens online for the affected product and version
  • In all other cases avoid the installation of the extension module from existing deliveries of Desigo CC or Desigo CC Compact software, until you receive an updated version of the software that already includes the patch

As a general security measure Siemens recommends protecting network access to affected products with appropriate mechanisms. It is advised to follow recommended security practices to run the devices in a protected IT environment.

For additional information, please refer to Siemens Security Advisory SSA-786743.