The vulnerabilities are permissive cross-domain policy with untrusted domains, cross-site scripting, classic buffer overflow, and improper input validation.
Successful exploitation of these remotely exploitable vulnerabilities, which Siemens self-reported, could lead to a restart of the UMC server.
Siemens reports the following products suffer from the vulnerabilities:
- Opcenter Quality: all versions
- SIMATIC PCS neo: versions prior to v4.1
- SINUMERIK Integrate RunMyHMI /Automotive: all versions
- Totally Integrated Automation Portal (TIA Portal) v14: all versions
- Totally Integrated Automation Portal (TIA Portal) v15.1: all versions
- Totally Integrated Automation Portal (TIA Portal) v16: all versions
- Totally Integrated Automation Portal (TIA Portal) v17: all versions
- Totally Integrated Automation Portal (TIA Portal) v18: versions prior to V18 update 3
In one issue, when accessing the UMC Web-UI from affected products, UMC uses an overly permissive CORS policy. This could allow an attacker to trick a legitimate user to trigger unwanted behavior.
CVE-2023-46281 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 7.1.
In addition, a reflected cross-site scripting vulnerability exists in the web interface of the affected applications that could allow an attacker to inject arbitrary JavaScript code. The code could potentially execute later by another (possibly privileged) user.
CVE-2023-46282 is the case number for this vulnerability, which has a CVSS v3 base score of 7.1.
Also, the affected application contains an out-of-bounds write past the end of an allocated buffer when handling specific requests on port 4002/tcp. This could allow an attacker to crash the application. The corresponding service auto-restarts after the crash.
CVE-2023-46283 is the case number for this vulnerability, which has a CVSS v3 base score of 7.5.
Meanwhile, the affected application contains an out-of-bounds write past the end of an allocated buffer when handling specific requests on port 4002/tcp and 4004/tcp. This could allow an attacker to crash the application. The corresponding service auto-restarts after the crash.
CVE-2023-46284 is the case number for this vulnerability, which has a CVSS v3 base score of 7.5.
In addition, the affected application contains an improper input validation vulnerability that could allow an attacker to bring the service into a denial-of-service state by sending a specifically crafted message to 4004/tcp.
CVE-2023-46285 is the case number for this vulnerability, which has a CVSS v3 base score of 7.5.
The product sees use mainly in the critical manufacturing sector, and on a global basis.
No known public exploits target these vulnerabilities. However, an attacker could leverage these low complexity vulnerabilities.
Siemens released updates for several affected products and recommends users update to the latest versions. Siemens is preparing further updates and recommends specific countermeasures for products where updates are not, or not yet available.
- SIMATIC PCS neo: Update to V4.1 or later version
- Totally Integrated Automation Portal (TIA Portal) V18: Update to V18 Update 3 or later version
Siemens identified the following workarounds and mitigations users can apply to reduce risk:
- Do not access links from untrusted sources.
- If using only one UMC server, block access to port 4002/tcp e.g. with an external firewall.
- If using only one RT server, block access to port 4004/tcp e.g. with an external firewall. If the deployment contains no RT-Servers, block the port in the local firewall.
As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens’ operational guidelines for industrial security and following recommendations in the product manuals.
For more information see the associated Siemens security advisory SSA-999588.