WAGO has new firmware to handle multiple vulnerabilities in its I/O-CHECK Series PFC100 and Series PFC200, according to a report with CISA.

The remotely exploitable vulnerabilities include an information exposure through sent data, buffer access with incorrect length value, missing authentication for critical function, and a classic buffer overflow.

Successful exploitation of these vulnerabilities, discovered by Kelly Leuschner of Cisco Talos, could allow an attacker to change settings, delete the application, run remote code, cause a system crash, cause a denial-of-service condition, revert to factory settings, and overwrite MAC addresses.

The following versions of I/O-CHECK software suffer from the vulnerabilities:

  • Series PFC100 (750-81xx/xxx-xxx)
  • Series PFC200 (750-82xx/xxx-xxx)
  • 750-852, 750-831/xxx-xxx, 750-881, 750-880/xxx-xxx, 750-889
  • 750-823, 750-832/xxx-xxx, 750-862, 750-890/xxx-xxx, 750-891
  • In one vulnerability, a specially crafted packet could cause the server to send back packets containing data from the stack.

    CVE-2019-5073 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 5.3.

    In addition, the affected products are vulnerable to a buffer overflow condition due to the lack of input validation, which may allow remote execution of arbitrary code.

    CVE-2019-5074 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 9.8.

    Also, the affected products are vulnerable to a buffer overflow condition due to the lack of input validation, which may allow remote execution of arbitrary code.

    CVE-2019-5075 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 9.8.

    In another issue, an attacker can send an unauthenticated packet that will overwrite the MAC address stored persistently on the device. This can cause the device to enter an error state where it ceases all network communications.

    CVE-2019-5077 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 10.0.

    In addition, an attacker can send an unauthenticated packet that will erase system data on the device. This may cause the device to enter an error state where it ceases all network communications.

    CVE-2019-5078 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 10.0.

    Also, the affected products are vulnerable to a buffer overflow condition due to the lack of input validation, which may allow remote execution of arbitrary code.

    CVE-2019-5079 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 10.0.

    In another issue, an attacker can send unauthenticated packets that will cause the device to restore factory settings. This may cause the device to enter an error state where it ceases all network communications.

    CVE-2019-5080 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 10.0.

    In addition, lack of input validation may allow an attacker to trigger a buffer overflow condition by sending unauthenticated packets to the device, which may allow remote execution of arbitrary code.

    CVE-2019-5081 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 10.0.

    Also, the affected products are vulnerable to a buffer overflow condition due to the lack of input validation, which may allow remote execution of arbitrary code.

    CVE-2019-5082 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 10.0.

    The product sees use mainly in the commercial facilities, energy, manufacturing, and transportation systems sectors. It also sees action on a global basis.

    No known public exploits specifically target these vulnerabilities. However, an attacker with low skill level could leverage the vulnerabilities.

    Germany-based WAGO recommends updating to the latest firmware, FW 15 or above.
    WAGO also found the following specific workarounds and mitigations users can apply to reduce the risk:

  • The I/O-Check service protocol is only needed during installation and commissioning, not during normal operations
  • It is highly recommended to disable IP Port 6626 after commissioning
  • Disable unused TCP/UDP-ports
  • Restrict network access to the device
  • Do not directly connect the device to the Internet