After attackers attacked a programmable logic controller (PLC) at a Pennsylvania water treatment facility, the feds are issuing a widespread warning for other users of the specific device.

That is because the Cybersecurity and Infrastructure Security Agency (CISA) is reacting to an active exploitation of a Unitronics-branded PLC used in the water and wastewater systems sector. The Municipal Water Authority of Aliquippa, Pennsylvania’s booster stations suffered a pump shut down after a hack attack. The attack was attributed to an Iranian-backed cyber group. Cyber threat actors targeted the Unitronics PLC connected to the pump.

In response, the affected municipality’s water authority immediately took the system offline and switched to manual operations. There was no risk to the municipality’s drinking water or water supply.

Water sector facilities use PLCs to control and monitor various stages and processes of water and wastewater treatment. That includes turning on and off pumps to fill tanks and reservoirs, flow pacing chemicals to meet regulations, gathering compliance data for monthly regulation reports, and announcing critical alarms to operations.

Compromising system integrity via unauthorized access threaten the ability of facilities to provide clean, potable water to  effectively manage the wastewater.

Schneider Bold

Attackers likely accessed the affected device – a Unitronics Vision Series PLC with a Human Machine Interface  – by exploiting cybersecurity weaknesses. Those weaknesses included poor password security and exposure to the Internet. To secure water and wastewater facilities against this threat, CISA urges organizations to:

  • Change the Unitronics PLC default password – validate the default password “1111” is not in use.
  • Require multifactor authentication for all remote access to the OT network, including from the IT network and external networks.
  • Disconnect the PLC from the open Internet. If remote access is necessary, implement a Firewall/VPN in front of the PLC to control network access to the remote PLC. A VPN or gateway device can enable multifactor authentication for remote access even if the PLC does not support multifactor authentication. Unitronics also has a secure cellular based longhaul transport device that is secure to their cloud services.
  • Back up the logic and configurations on any Unitronics PLCs to enable fast recovery. Become familiar with the process for factory resetting and deploying configurations to a device in the event of being hit by ransomware.
  • If possible, utilize a TCP port that is different than the default port TCP 20256. Cyber actors are actively targeting TCP 20256 after identifying it through network probing as a port associated to Unitronics PLC. Once identified, they leverage scripts specific to PCOM/TCP to query and validate the system, allowing for further probing and connection. If available, use PCOM/TCP filters to parse out the packets.
  • Update PLC/HMI to the latest version provided by Unitronics.

Pin It on Pinterest

Share This