But one of the keys to a growing hydrogen environment is keeping the energy-producing infrastructure safe.
Along those lines, the Korea Institute of Civil Engineering and Building Technology, a South Korea government sponsored research institute, released its plan to develop technologies related to an underground hydrogen infrastructure project in the country, from its design and construction to its operation and management.
These technologies would fundamentally improve the safety of hydrogen facilities.
A safe and reliable infrastructure is crucial to establishing a hydrogen ecosystem. However, any ground-level hydrogen facility project tends to face fierce opposition from local residents, and the alternative to building them underground makes the project less cost-effective and efficient.
Until now. That is because Dr. Kim Yangkyun of the Hydrogen-infrastructure Research Cluster at KICT developed the core safety engineering technologies for building reliable hydrogen infrastructure underground along with an active control system to mitigate the impact of possible hydrogen leaks and blasts.
The new system can help control the ambient hydrogen concentration within an underground facility at all times via forced ventilation and can reduce risk up to 80 percent compared with similar above-ground facilities thanks to the introduction of roof-type vents that minimize blast overpressure in times of an emergency.
Basically, any underground hydrogen infrastructure is an enclosed space.
All risks of a potential blast should be eliminated by keeping the ambient hydrogen concentration below the Lower Flammable Limit (LFL) whenever a leak occurs.

Hydrogen explosion test conducted in an enclosure consisting of reinforced concrete and almost sealed. Hydrogen supplied into enclosure was 20 percent. This series of photo shows structure damage due to evolution of deflagration in enclosure just after ignition.
Source: Korea Institute of Civil Engineering and Building Technology
The active control system Yangkyun’s research team proposed maintains the quality of the atmosphere of the enclosed space to a normal level and can prevent blast accidents at times of emergency hydrogen gas leaks. An optimized interpretation was used, including multiple factors (shape, location, intake, and outtake capacities of the inlet/outlet) to formulate the conditions for ordinary times and for an emergency where the concentration of hydrogen gas in the facility is kept below the LFL or 4 percent of hydrogen by volume.
If the active control system malfunctions and an explosion occurs, such an impact should be minimal. The roof-type vent of the deflagration venting system can reduce damage from blast overpressure inside the facility to a 20th. The real-scale experiment of vented deflagration conducted at KICT in 2021 showed the maximum overpressure reduction effect could be obtained due to a sudden drop in blast overpressure when the explosion vent is bigger than the vent coefficient standard of 2.2.
The effectiveness remained constant regardless of the hydrogen concentration or point of the deflagration.
Another model was presented to calculate the size of the roof-type vent for the safe design of the underground hydrogen facility. The improved model was built on the minimum vent size model specified in guide NFPA68 of the U.S. National Fire Protection Association to apply to underground hydrogen facilities. The research team focused on the fusion of functions: Ventilations in normal time and after a blast accident.
“The dual system of active control ventilation and the roof type vent is an integrated security technology for both emergency and non-emergency situations responding to all risks incurred in an accident by making the most of the limited cross-section area of the vent,” Yangkyun said.