There was an incident offshore involving the separation of a section of fiber reinforced plastic pipe (FRP) from its flange.

As a safety precaution, officials immediately halted production to investigate the situation, according to a report from the Bureau of Safety and Environmental Enforcement (BSEE).

During the inspection, the team discovered that a segment of 10-inch FRP piping disengaged from its attached flange, resulting in a 4-inch pipe also becoming detached due to the movement of the 10-inch pipe.

To address the issue, the affected fire loop main promptly ended up isolated from the rest of the system, allowing the remainder of the system to resume normal operation. Workers swiftly repaired the fire main, and once they completed the necessary repairs, production at the facility resumed.

The operator identified a bond failure as a potential cause of the separation, which subsequently ended up addressed to prevent the incident from happening again.

Schneider Bold
  • As a result of the incident, BSEE recommends operators and contractors consider the following:
  • Review preventative maintenance records and ensure adequate inspection and routine checks of firefighting equipment.
  • Photos show a segment of 10-inch FRP piping disengaged from its attached flange, which resulted in a 4-inch pipe also becoming detached.
    Source: BSEE

  • Providing instructions, training, competency assessments, and proper supervision to operators and maintenance personnel.
    Testing, if possible, the connection between the FRP pipe and flange to ensure an adequate seal.
  • Visually checking for leaks while the mains pressurize during routine firewater system tests. According to regulations for fire water systems (as per API RP 14G 4th Edition, Section 5.2), it is essential to maintain sufficient pressure (a minimum of 75 psig) when hose streams are flowing, unless the nozzle manufacturer specifies higher pressure requirements. Even a fire water system with small leaks may initially meet the pressure requirement, but addressing smaller leaks promptly can prevent more significant failures from occurring