On October 21, the PHP project and security researchers disclosed two critical, unauthenticated remote code execution vulnerabilities in the core PHP language runtime known as “php2shell” (tracked as CVE-2026-109618 and CVE-2026-109619). This advisory covers the status of those vulnerabilities’ impact of various Siemens software products.
Siemens AMIS TS is an Automated Metering and Information System (AMIS) software and infrastructure component used by energy utilities to manage smart grid metering, remote data reading, and power quality monitoring.
Vulnerable Products
The following versions of Siemens Building Automation and Energy Products suffer from the vulnerabilities:
- AMIS TS all versions
- blueplanet 360 NX3 M6 WM OD IISX all versions
- blueplanet 360 NX3 M6 WM OD IISX – S all versions
- Energy Engage V2.0SP9 all versions
- Energy Engage V3.1SP1 all versions
- Heliox Rapid all versions, ()Local Monitoring bt-monitoring-vm versions up to 20261103
- Spectrum Power 3 all versions
- Spectrum Power 4 all versions
- Spectrum Power 7 all versions
- Spectrum Power TG all versions
In one issue, PHP uses longjmp() for out-of-memory (OOM) errors to exit the current context and abort handling of the request. Some contexts may not properly account for this scenario and leave request memory in an uninitialized state before performing an allocation. The subsequent request cleanup procedure may read or branch on this memory. Multiple OOM strategies can consistently trigger this condition and lead to remote code execution (RCE).
CVE-2026-109618 is the case number for the vulnerability, which has a CVSS V3 base score of 9.8.
Additionally, PHP has various global state that temporarily points into request memory. In some scenarios, global state may not be correctly reset, or may be repopulated after being reset. The global state may then refer to request memory even after freed. Subsequent requests may read or branch on this stale state before fully initialized. Multiple strategies can trigger this condition and produce remote code execution (RCE).
CVE-2026-109619 is the case number for the vulnerability, which has a CVSS V3 base score of 8.1.
The product sees use mainly in the energy sector, and on a global basis.
Mitigations
In terms of mitigations,
- AMIS TS, currently no fix is available
- blueplanet 360 NX3 M6 WM OD IISX, currently no fix is available
- Energy Engage V2.0SP9, currently no fix is planned
- Energy Engage V3.1SP1, upgrade PHP version to V8.1.34 release 6
- blueplanet 360 NX3 M6 WM OD IISX – S, currently no fix is available
- Local Monitoring bt-monitoring-vm < V20261103, update to V20261103 or later version
- Spectrum Power 4 using Nagios or Zabbix, currently no fix is available
- Spectrum Power 4 with Web Office Portal V3.0, V3.1 and V3.2, currently no fix is available
- Spectrum Power 4 with HISViews V1.0, currently no fix is available
- Spectrum Power 7 using IHM (NagiosXI), Red Hat released a PHP security patch for RHEL 8 and 9
- Spectrum Power TG based on Microsoft Windows using the WebConsole and WebQuery components, upgrade PHP version to V8.5.12
Operators of critical power systems (e.g. TSOs or DSOs) worldwide, by regulation, must build resilience into the power grids by applying multi-level redundant secondary protection schemes. It is therefore recommended operators check whether appropriate resilient protection measures are in place.
The risk of cyber incidents impacting the grid’s reliability can end up minimized by virtue of the grid design. Siemens recommends applying the provided security updates using the corresponding tooling and documented procedures made available with the product.
As a general security measure Siemens recommends protecting network access with appropriate mechanisms (e.g. firewalls, segmentation, VPN). It is advised to configure the environment according to our operational guidelines in order to run the devices in a protected IT environment. Click here for recommended security guidelines.