This pattern has given rise to safety incidents, such as fires and arc flashes, underscoring the vital importance of averting these electrical hazards, said officials at the Bureau of Safety and Environmental Enforcement (BSEE).
Poor electrical connections pose a common and significant fire hazard, as they have the potential to generate substantial heat without significantly impeding electric current flow. This renders fuses and circuit breakers ineffective, allowing for escalation of the hazard. It is crucial to address these issues promptly and comprehensively to maintain a safe working environment.
One incident involved a complete power loss of a temporary generator within the production facility. Upon investigation, the platform electrician identified the 480-volt alternating current (VAC) #2 phase cable had melted off at the generator bus connection.
This was attributed to a loose cable connection at the cable lug. In response to the situation, power ended up switched over to the platform’s emergency generator. Fortunately, there were no injuries or damage beyond the wiring.
The root cause of the incident traced back to the faulty cable connection at the cable lug, leading to excessive heat generation and subsequent cable melting.
In a second incident, the issue unfolded during a routine nighttime equipment check at a production facility. Crew members detected smoke emerging from a gap in the insulation near the inlet flange on the second flanged section of a fuel gas line run.
Workers alerted an electrician who was able to take immediate action by turning off the breaker in the junction box, which supplied power to the heat trace section, ensuring a termination of all power. To prevent smoldering, the crew soaked the insulation with water.
Upon subsequent investigations, a break in the heat trace cable insulation on the inlet flange of the gas volume bottle was found.
The root cause of this incident traced back to the failure of the breaker to terminate power to the heat trace, attributed to improper grounding. This failure resulted in excessive heat and smoldering of insulation.
In a third incident, personnel conducting daily checks during a rainstorm heard a sudden popping sound, which prompted immediate investigations and revealed wires arcing at the junction box (400 Automatic Transfer Switch (ATS)) for the gas generator.
Workers promptly initiated an emergency shutdown for the gas generator, activating the emergency diesel generator to supply power to the facility. Personnel strictly followed Lockout/Tagout (LO/TO) procedures as part of the emergency shutdown protocol. All valves to vessels on the facility ended up isolated and stop work authority came into play to ensure immediate safety.
Workers discovered the top cable on the ATS from the platform diesel generator lacked a traditional drip loop. This absence allowed rainwater to flow onto the live power cable below, leading to its failure.
Although designed to withstand weather, the improperly installed cable, exposed to constant sun and rain without adequate protection, developed small fractures in its casing. Over an undetermined number of years, rainwater seeped into the cable, causing material fatigue, and ultimately resulting in the cable’s failure during a thunderstorm.
As a result of these incidents, BSEE recommends operators and their contractors:
- Implement a routine inspection and maintenance schedule for cable connections to ensure secure and correct function
- Ensure personnel involved in cable connections and maintenance receive proper training and understand the importance of secure and reliable connections
- Communicate and rehearse emergency response procedures, such as switching over to emergency generators, in case of power-related incidents
Review and enhance existing procedures for connecting and securing cables - Review and reinforce LO/TO procedures to ensure the safe and secure isolation of electrical components during maintenance and investigations
- Conduct periodic thermographic inspections using a forward-looking infrared (FLIR) camera to identify any signs of overheating or loose connections
- Utilize locking type connections in areas where fouling of electrical lines due to water ingress is a risk