Natural gas compressor stations are critical for maintaining pressure and flow in long-distance transmission pipelines. These facilities often contain multiple high-power compressors housed in ventilated enclosures, where leaks or fires present significant operational and safety risks.
To safeguard personnel, equipment, and continuous operations, a major Australian pipeline operator sought a highly reliable and SIL 2 capable logic solver solution to manage fire and gas (F&G) protection at a new compressor station. Each compressor enclosure needed local detection, alarming, and emergency shutdown (ESD) capabilities, as well as seamless integration with the site’s PLC and centralized SCADA system.
Key requirements of the safety instrumented system are to:
- Monitor multiple fire and gas detectors across two independent compressor enclosures
- Provide local hardwired trip and shutdown logic with complex voting schemes (1oo2, 2oo2, and 4oo4)
- Trigger site-wide ESD and evacuation alerts when dangerous gas or fire conditions end up confirmed
- Integrate with the site PLC via MODBUS/TCP, enabling centralized monitoring and diagnostics from a remote gas operations SCADA center
- Meet specified safety requirements with fail-safe performance and high reliability
In this case, the SLA Multifunctional Safety Logic Solver and Alarm from Moore Industries ended up selected as the logic solver for each compressor enclosure. The reasoning was because of its IEC 61508 Functional Safety Certification and SIL capability. Moreover, it also had a compact design, flexible logic programming, and proven reliability in safety-critical applications.

An operator for a new compressor station needed a reliable and SIL 2 capable logic solver solution to manage fire and gas protection.
Source: Moore Industries
SLA Installation
The results of installing the SLA:
- Showed each SLA processed four 4-20mA signals from connected fire and gas detectors, with the flexibility to accommodate up to six inputs as needed.
- Supported complex logic conditions such as high-high gas trip (LEL less than 40 percent) and confirmed fire (19mA), with voting combinations (1oo2, 2oo2.)
- Generated four hardwired relay outputs (RO1–RO4) for gas trip, detector faults, fire trip, and emergency shutdown.
- Transmitted 16 soft alarms via MODBUS/TCP to the site PLC, including detector diagnostics (dirty window, power fault, general fault).
- Delivered a highly reliable SIL 2 capable logic solver solution for fire and gas protection.
When the operator met all high-high gas and fire trip conditions, the SLA initiated an emergency shutdown of the compressor string. Additionally, it activated the site-wide siren and beacon system, giving personnel time to evacuate.
Fire and gas hazards are among the most serious risks in natural gas compressor stations. By deploying the SLA Multifunctional Safety Logic Solver and Alarm, the pipeline operator achieved a compact, reliable, and SIL 2 capable logic solver solution that integrates local shutdown protection and remote supervisory visibility.