A chemical facility had safety variables connected to the Safety Instrumented System (SIS), but they wanted to add those variables to their MODBUS Host.

The safety variables they wanted to share were from HART devices like the Functional Safety HART Temperature Transmitters.

That is where Moore Industries’ HES HART to Ethernet Gateway System came into play as a multichannel HART-to-MODBUS converter. The catch is, though, it cannot connect to the safety loops directly as that would negatively affect the user’s loop reliability per IEC 61511 guidelines.

But by adding a SSX HART Functional Safety Isolator to each safety loop, it was possible to provide air-gap isolation between the safety loop and the HART-to-MODBUS converter. In this case, the exida approved SIL 3 capable SSX had certification for use in safety functions. The isolator allows the HART digital signal to cross the air-gap isolation.

The output of each safety isolator can then wire into three of the four channels on the HES HART-to-MODBUS converter. The HES reads the HART dynamic variables and diagnostic data of the STZ Temperature Transmitter and maps them to MODBUS registers awaiting the communication request from the MODBUS Host.

Schneider Bold

The SSX safety isolator can end up being a tool to get more functionality from safety systems.

Key elements to the system include:

  • HART-to-MODBUS conversion with the HES
  • Isolation from SIS with SIL-3 capable SSX Isolator
  • All dynamic variables and diagnostics end up safely delivered from the temperature transmitters in the safety loop to the SCADA System via MODBUS/TCP

Click here for more HES information.

Safety variables

The exida approved, SIL 3 capable SSX has certification for use in safety functions.
Source: Moore Industries