In this application, to mitigate high-risk conditions due to out-of-specification acid concentration levels, a Safety Integrity Level 2 (SIL 2) Safety Instrumented Function (SIF) could end up implemented using a SLA Safety Logic Solver and Alarm.
Redundant flow and acid concentration transmitters end up monitored by the SLA, along with the status of acid pumps and demineralized shutoff valves. To ensure proper safety coverage, continuous monitoring of several variables and advanced alarming and logic is a requirement.
The SLA has several inputs and 16 internal alarms which can end up configured to monitor flow and acid concentration levels from the redundant transmitters.
Additionally, six digital inputs end up fed into the SLA which report acid pump run status and demineralized water shutoff valve status. The SLA’s internal alarm statuses or outputs, along with the digital inputs, can then create internal logic equations using simple to configure Excel-like formulas to generate more advanced alarm scenarios.
The Moore Industries’ SLA then uses these advanced internal alarms to create a 1oo2 voting logic strategy to determine when it is necessary to trigger the shutoff valves via its relay outputs. In addition, all inputs, outputs and internal variables and alarms can end up monitored via the SLA’s read only web server or communicated to a remote host by MODBUS/TCP or MODBUS RTU.
Key attributes include:
- 16 internal alarms and 16 internal logic equations aid in advanced shutdown strategy
- Simple to configure 1oo2 voting alarm logic with check boxes and pill-down menus
- SLA is SIL 2/3 capable and exida approved to IEC 61508:2010 standard
- Accepts six Digital Inputs to monitor pump run status and open/closed status of valves