Failure to appropriately control pressure can result in catastrophic equipment damage, environmental damage, and potentially fatal outcomes.
To mitigate such hazards, a High Integrity Pressure Protection System (HIPPS) ends up used like the Moore Industries SLA Multiloop and Multifunctional Logic Solver in a 2oo3 (two-out-of-three) voting architecture. This configuration ensures reliability and availability of wellhead shutdown in response to overpressure conditions.
The HIPPS shutdown system incorporates the following key components:
- Three Smart HART Pressure Transmitters (0-10,000 psi range)
- Moore Industries SLA Multiloop and Multifunctional Logic Solver
- Remote Terminal Unit (RTU) or Programmable Logic Controller (PLC)
- Emergency Shutdown (ESD) Valve
In this architecture, three pressure transmitters continuously monitor wellhead pressure. These transmitters directly connect to the SLA, which evaluates the signals and performs a 2oo3 voting decision. If at least two of the three pressure transmitters detect a pressure of 8,700 psi or higher, the SLA initiates a wellhead shutdown by triggering the ESD valve.
The SLA’s built-in loop power supply on each of its three channels provides operating power to all three smart HART pressure transmitters. The HART signal from the three pressure transmitters passes through to each of the SLA’s corresponding analog outputs so the RTU/PLC has direct access to all HART programming, variables, and diagnostics of each connected transmitter.
Higher Availability
Meanwhile, the retransmission of these three pressure transmitters by the SLA, versus wiring in series with the RTU/PLC input cards, provides higher availability to the safety function since a catastrophic failure in the analog input cards or the RTU/PLC itself doesn’t affect the 2oo3 logic shutdown function of the SLA.

Application illustration showing the SLA with three pressure inputs, three relay outputs drive by an alarm voting strategy; three analog outputs connecting to a RTU/PLC system to monitor each zone’s pressure; and all inputs, outputs, alarms, faults, and other parameters from the SLA transmitted via MODBUS RTU to the RTU/PLC.Source: Moore Industries
Moreover, additional relay outputs of the SLA also keep the RTU/PLC informed of shutdown status and any input faults experienced by the SLA. Additionally, a digital contact input allows any alarm or relay configured as latching to be manually reset.
Finally, all inputs, outputs, internal equations, variables, alarms, relay status and more are digitally transmitted to the RTU/PLC via a read-only MODBUS RTU signal.
Furthermore, as oil and gas operations demand stricter safety requirements, SLA-based HIPPS offers a solution for reducing overpressure hazards while increasing system uptime and process efficiency.